| 2020-12-14 16:01:07 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) PLEASE PROVIDE A COMPLETE SCOPE OF WORK FOR THIS |
| | PROJECT. |
| | |
| | IT APPEARS THAT THE ENTIRE BUILDING IS BEING REMODELED |
| | WHICH WOULD BE REQUIRED TO BE CONSTRUCTED A A NEW |
| | OCCUPANCY. |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | |
| | 2) THERE IS NO INDICATION OF COMPLAINCE WITH ANY FIRE |
| | CODES. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH |
| | INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101. |
| | |
| | THE BELOW LIST ARE THE MOST COMMON REFERENCED CODES: |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2013 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2013 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2013 EDITION. |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2013 EDITION. |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF REVIEW AND |
| | COMPLIANCE. |
| | |
| | |
| | |
| | 3) PLEASE PROVIDE THE NEW OCCUPANCY TYPE AS IT APPEARS |
| | TO BE AN APARTMENT OCCUPANCY AND COMPLY WITH THE |
| | REQUIRMENTS OF NFPA 30. |
| | |
| | CHAPTER 30 NEW APARTMENT BUILDINGS |
| | 30.1 GENERAL REQUIREMENTS. |
| | 30.1.1 APPLICATION. |
| | 30.1.1.1 THE REQUIREMENTS OF THIS CHAPTER SHALL APPLY |
| | TO NEW |
| | BUILDINGS OR PORTIONS THEREOF USED AS APARTMENT |
| | OCCUPANCIES. (SEE |
| | 1.3.1.) |
| | |
| | PLEASE PROVIDE DETAILS |
| | |
| | |
| | |
| | 4) THERE ARE NO INDICATIONS OF A FIRE SPRINKLER SYSTEM |
| | |
| | 30.3.5 EXTINGUISHMENT REQUIREMENTS. |
| | 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY |
| | AN APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM INSTALLED IN |
| | ACCORDANCE WITH |
| | 30.3.5.2. |
| | 30.3.5.2 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS |
| | INSTALLED, EITHER FOR |
| | TOTAL OR PARTIAL BUILDING COVERAGE, THE SYSTEM SHALL BE |
| | INSTALLED IN |
| | ACCORDANCE WITH SECTION 9.7, AS MODIFIED BY 30.3.5.3 |
| | AND 30.3.5.4. IN |
| | BUILDINGS FOUR OR FEWER STORIES ABOVE GRADE PLANE, |
| | SYSTEMS IN |
| | ACCORDANCE WITH NFPA 13R, STANDARD FOR THE INSTALLATION |
| | OF |
| | SPRINKLER SYSTEMS IN LOW-RISE RESIDENTIAL OCCUPANCIES, |
| | SHALL BE |
| | PERMITTED. |
| | |
| | REQUIRED F.A.C. 61G ARE REQUIRED TO BE SUBMITTED WITH |
| | THIS MASTER PERMIT. |
| | |
| | PLEASE PROVIDE. |
| | |
| | |
| | 5) THERE ARE NO INDICATIONS OF A FIRE ALARM SYSTEM. |
| | |
| | A FIRE SPRINKLER ALARM IS REQUIRED AND SHALL BE |
| | MONITORED. |
| | |
| | 9.7.2 SUPERVISION. |
| | 9.7.2.1* SUPERVISORY SIGNALS. |
| | 9.7.2.1.1 WHERE SUPERVISED AUTOMATIC SPRINKLER SYSTEMS |
| | ARE REQUIRED BY |
| | ANOTHER SECTION OF THIS CODE, SUPERVISORY ATTACHMENTS |
| | SHALL BE INSTALLED |
| | AND MONITORED FOR INTEGRITY IN ACCORDANCE WITH NFPA 72, |
| | NATIONAL FIRE |
| | ALARM AND SIGNALING CODE, AND A DISTINCTIVE SUPERVISORY |
| | SIGNAL SHALL BE |
| | PROVIDED TO INDICATE A CONDITION THAT WOULD IMPAIR THE |
| | SATISFACTORY |
| | OPERATION OF THE SPRINKLER SYSTEM. |
| | 9.7.2.1.2 SUPERVISORY SIGNALS SHALL SOUND AND SHALL BE |
| | DISPLAYED EITHER AT |
| | A LOCATION WITHIN THE PROTECTED BUILDING THAT IS |
| | CONSTANTLY ATTENDED BY |
| | QUALIFIED PERSONNEL OR AT AN APPROVED, REMOTELY LOCATED |
| | RECEIVING |
| | FACILITY. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDEGMENT |
| | |
| | |
| | 6) THERE APPEARS TO BE A SIGNLE EXIT FROM THE 3RD FL |
| | UNIT. |
| | |
| | 2 ARE REQUIRED. |
| | |
| | 30.2.4 NUMBER OF MEANS OF EGRESS. |
| | 30.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL COMPLY |
| | WITH |
| | SECTION 7.4. |
| | 30.2.4.2 THE MINIMUM NUMBER OF EXITS SHALL COMPLY WITH |
| | 30.2.4.3, 30.2.4.4, OR 30.2.4.6. |
| | 30.2.4.3 EVERY DWELLING UNIT SHALL HAVE ACCESS TO AT |
| | LEAST TWO |
| | SEPARATE EXITS REMOTELY LOCATED FROM EACH OTHER AS |
| | REQUIRED BY |
| | 7.5.1. |
| | 30.2.4.4 DWELLING UNITS SHALL BE PERMITTED TO HAVE |
| | ACCESS TO A |
| | SINGLE EXIT, PROVIDED THAT ONE OF THE FOLLOWING |
| | CONDITIONS IS MET: |
| | (1) THE DWELLING UNIT HAS AN EXIT DOOR OPENING DIRECTLY |
| | TO THE |
| | STREET OR YARD AT THE FINISHED GROUND LEVEL. |
| | (2) THE DWELLING UNIT HAS DIRECT ACCESS TO AN OUTSIDE |
| | STAIR THAT |
| | COMPLIES WITH 7.2.2 AND SERVES A MAXIMUM OF TWO UNITS, |
| | BOTH OF WHICH ARE LOCATED ON THE SAME STORY. |
| | (3) THE DWELLING UNIT HAS DIRECT ACCESS TO AN INTERIOR |
| | STAIR THAT |
| | SERVES ONLY THAT UNIT AND IS SEPARATED FROM ALL OTHER |
| | PORTIONS |
| | OF THE BUILDING BY FIRE BARRIERS HAVING A MINIMUM |
| | 1-HOUR FIRE |
| | RESISTANCE RATING, WITH NO OPENING THEREIN. |
| | |
| | 30.2.4.6 A SINGLE EXIT SHALL BE PERMITTED IN BUILDINGS |
| | WHERE THE |
| | TOTAL NUMBER OF STORIES DOES NOT EXCEED FOUR, PROVIDED |
| | THAT ALL OF |
| | THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THERE ARE FOUR OR FEWER DWELLING UNITS PER STORY. |
| | (2) THE BUILDING IS PROTECTED THROUGHOUT BY AN |
| | APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH |
| | 30.3.5. |
| | (3) THE EXIT STAIRWAY DOES NOT SERVE MORE THAN ONE-HALF |
| | STORY |
| | BELOW THE LEVEL OF EXIT DISCHARGE. |
| | (4) THE TRAVEL DISTANCE FROM THE ENTRANCE DOOR OF ANY |
| | DWELLING |
| | UNIT TO AN EXIT DOES NOT EXCEED 35 FT (10.7 M). |
| | (5) THE EXIT STAIRWAY IS COMPLETELY ENCLOSED OR |
| | SEPARATED FROM |
| | THE REST OF THE BUILDING BY BARRIERS HAVING A MINIMUM |
| | 1-HOUR |
| | FIRE RESISTANCE RATING. |
| | (6) ALL OPENINGS BETWEEN THE EXIT STAIRWAY ENCLOSURE |
| | AND THE |
| | BUILDING ARE PROTECTED WITH SELF-CLOSING DOOR |
| | ASSEMBLIES |
| | HAVING A MINIMUM 1-HOUR FIRE PROTECTION RATING. |
| | (7) ALL CORRIDORS SERVING AS ACCESS TO EXITS HAVE A |
| | MINIMUM 1- |
| | HOUR FIRE RESISTANCE RATING. |
| | (8) HORIZONTAL AND VERTICAL SEPARATION HAVING A MINIMUM |
| | ?-HOUR |
| | FIRE RESISTANCE RATING IS PROVIDED BETWEEN DWELLING |
| | UNITS. |
| | |
| | PLEASE CORRECT OR PROVIDE DETAILS IN COMPLIANCE. |
| | |
| | |
| | 7) THERE ARE INDICATIONS OF STAIR EXIT PAST UNPROTECTD |
| | WINDOWS. |
| | |
| | 30.2.2.3 STAIRS. |
| | 30.2.2.3.1 STAIRS COMPLYING WITH 7.2.2 SHALL BE |
| | PERMITTED. |
| | |
| | 7.2.2.6.3 SEPARATION AND PROTECTION OF OUTSIDE STAIRS. |
| | 7.2.2.6.3.1* OUTSIDE STAIRS SHALL BE SEPARATED FROM THE |
| | INTERIOR OF THE |
| | BUILDING BY CONSTRUCTION WITH THE FIRE RESISTANCE |
| | RATING REQUIRED FOR |
| | ENCLOSED STAIRS WITH FIXED OR SELF-CLOSING OPENING |
| | PROTECTIVES, |
| | EXCEPT AS FOLLOWS: |
| | (1) OUTSIDE STAIRS SERVING AN EXTERIOR EXIT ACCESS |
| | BALCONY THAT HAS |
| | TWO REMOTE OUTSIDE STAIRWAYS OR RAMPS SHALL BE |
| | PERMITTED TO BE |
| | UNPROTECTED. |
| | (2) OUTSIDE STAIRS SERVING TWO OR FEWER ADJACENT |
| | STORIES, INCLUDING |
| | THE STORY WHERE THE EXIT DISCHARGES, SHALL BE PERMITTED |
| | TO BE |
| | UNPROTECTED WHERE THERE IS A REMOTELY LOCATED SECOND |
| | EXIT. |
| | (3) IN EXISTING BUILDINGS, EXISTING OUTSIDE STAIRS |
| | SERVING THREE OR |
| | FEWER ADJACENT STORIES, INCLUDING THE STORY WHERE THE |
| | EXIT |
| | DISCHARGES, SHALL BE PERMITTED TO BE UNPROTECTED WHERE |
| | THERE IS |
| | A REMOTELY LOCATED SECOND EXIT. |
| | (4) THE FIRE RESISTANCE RATING OF A SEPARATION |
| | EXTENDING 10 FT (3050 |
| | MM) FROM THE STAIRS SHALL NOT BE REQUIRED TO EXCEED 1 |
| | HOUR |
| | WHERE OPENINGS HAVE A MINIMUM ?-HOUR FIRE PROTECTION |
| | RATING. |
| | (5) OUTSIDE STAIRS IN EXISTING BUILDINGS PROTECTED |
| | THROUGHOUT BY AN |
| | APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH SECTION 9.7 SHALL BE PERMITTED TO BE |
| | UNPROTECTED. |
| | 7.2.2.6.3.2 WALL CONSTRUCTION REQUIRED BY 7.2.2.6.3.1 |
| | SHALL EXTEND AS |
| | FOLLOWS: |
| | (1) VERTICALLY FROM THE FINISHED GROUND LEVEL TO A |
| | POINT 10 FT (3050 |
| | MM) ABOVE THE TOPMOST LANDING OF THE STAIRS OR TO THE |
| | ROOFLINE, |
| | WHICHEVER IS LOWER |
| | (2) HORIZONTALLY FOR NOT LESS THAN 10 FT (3050 MM) |
| | |
| | PLEASE REVIEW AND CORRECT AS APPLICABLE. |
| | |
| | |
| | 8) THERE ARE NO INDICATIONS OF STAIR DETAILS IN |
| | COMPLIANCE WITH THE FIRE CODE. |
| | |
| | 30.2.2.3 STAIRS. |
| | 30.2.2.3.1 STAIRS COMPLYING WITH 7.2.2 SHALL BE |
| | PERMITTED. |
| | |
| | 7.2.2.4 GUARDS AND HANDRAILS. |
| | 7.2.2.4.1 HANDRAILS. |
| | |
| | 7.2.2.4.5* HANDRAIL DETAILS. |
| | |
| | 7.2.2.4.6 GUARD DETAILS |
| | |
| | PLEASE PROVIDE SPECIFIC DETAILS OF COMPLIANCE. |
| | |
| | |
| | |
| | 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |