Plan Review Notes
Plan Review Notes For Permit 20050773
Permit Number 20050773
Review Stop B
Sequence Number 1
Notes
Date Text
2020-06-09 08:36:002017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20050773
 ADD: 300 AUSTRALIAN AVE. SUITE: 711
 CONT: FLOCKER CONSTRUCTION LLC
 TEL: 443-309-2328
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JUNE 09/2020
 ACTION: DENIED
  
 1) THE COVERSHEET LIST THE 2017 RESIDENTIAL CODE AS THE
 REFERENCED CODE. PLEASE BE AWARE CONDOMINIUMS IN
 HIGH-RISES ARE TO BE CODE COMPLIANT WITH THE 2017
 EXISTING BUILDING CODE AND THE 2017 FBC-BUILDING FOR A
 R2 OCCUPANCY GROUP.
  
 2) THE DESIGNER OF RECORD HAS NOT PROVIDED UNDER WHICH
 METHOD THE PLANS WERE DEVELOPED. . 2017 EXISTING BUILD.
 CODE SECTION 301.1. THE REPAIRS, ALTERATIONS, CHANGE OF
 OCCUPANCY, ADDITIONS OR RELOCATION OF ALL EXISTING
 BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS LISTED
 IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE
 DESIGNER OF RECORD.
  
 3) SHEET A1.0 INDICATES THE REMOVAL AND NEW
 INSTALLATION OF TILE IN THE TUB AND SHOWER. THE PLANS
 DO NOT INDICATE WHAT TYPE OF TILE BACKER BOARD IS TO BE
 INSTALLED IN THESE WET AREAS. PLEASE SHOW COMPLIANCE
 WITH THE 2017 FBC-B:
 2017 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS A
 BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE
 FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND
 THE MANUFACTURE?S RECOMMENDATIONS.
  
 4) FLOOR INSULATION (FBC-B 2017) FOR TILE, STONE,
 MARBLE, LUXURY VINYL FLOORING OR LUXURY VINYL PLANK
 FLOORING AND WOOD FLOORING ALL NEED SEPARATE TEST
 REPORTS FOR SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 TYPE I AND II BUILDINGS
 4A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4B) FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 4C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME IF YOU WOULD LIKE
 TO CONTACT ME, MY CELL NUMBER IS 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  