2020-06-09 12:30:43CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20050766 625 N FLAGLER DR # 625
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1. PER WPB FBC 107.2.1, PROVIDE ON PLANS THE
 LOCATION(S) OF MINIMUM PLUMBING FACILITIES FOR THE
 BUSINESS OCCUPANCY PER FBC PL 403.1, TABLE 403.1 AS
 FOLLOW:
 A. FBC PL 410.3 REQUIRES NO FEWER THAN TWO DRINKING
 FOUNTAINS. ONE DRINKING FOUNTAIN SHALL COMPLY WITH THE
 REQUIREMENTS FOR PEOPLE WHO USE A WHEELCHAIR AND ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS
 FOR STANDING PERSONS. A SINGLE DRINKING FOUNTAIN WITH
 TWO SEPARATE SPOUTS THAT COMPLIES WITH THE REQUIREMENTS
 FOR PEOPLE WHO USE A WHEELCHAIR AND STANDING PERSONS
 SHALL BE PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE
 DRINKING FOUNTAINS. COMPLY WITH FBC ACC 211.2 AND
 SECTION 602.
 B. ONE (1) SERVICE SINK
  
 2. THE BSL-2 RESEARCH LABORATORY SUMMARY SUBMITTED IN
 SUPPORTING DOCUMENTS CALL OUT AN AUTOCLAVE. PER WPB FBC
 107.2.1, PROVIDE MANUFACTURER?S
 SPECIFICATION/INSTALLATION MANUAL SHOWING COMPLIANCE
 WITH FBC PL 422.9 AND SHOW LOCATION ON THE PLANS.
 3. THE BSL-2 RESEARCH LABORATORY SUMMARY SUBMITTED IN
 SUPPORTING DOCUMENTS CALL OUT AND SHOW TWO (2)
 EMERGENCY EYEWASH STATIONS. PER WPB FBC 107.2.1,
 PROVIDE MANUFACTURER?S SPECIFICATION/INSTALLATION
 MANUAL SHOWING COMPLIANCE WITH FBC PL 411.1 AND SHOW
 LOCATIONS ON THE PLANS.
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  