| 2020-06-09 12:30:43 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20050766 625 N FLAGLER DR # 625 |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | 1. PER WPB FBC 107.2.1, PROVIDE ON PLANS THE |
| | LOCATION(S) OF MINIMUM PLUMBING FACILITIES FOR THE |
| | BUSINESS OCCUPANCY PER FBC PL 403.1, TABLE 403.1 AS |
| | FOLLOW: |
| | A. FBC PL 410.3 REQUIRES NO FEWER THAN TWO DRINKING |
| | FOUNTAINS. ONE DRINKING FOUNTAIN SHALL COMPLY WITH THE |
| | REQUIREMENTS FOR PEOPLE WHO USE A WHEELCHAIR AND ONE |
| | DRINKING FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS |
| | FOR STANDING PERSONS. A SINGLE DRINKING FOUNTAIN WITH |
| | TWO SEPARATE SPOUTS THAT COMPLIES WITH THE REQUIREMENTS |
| | FOR PEOPLE WHO USE A WHEELCHAIR AND STANDING PERSONS |
| | SHALL BE PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE |
| | DRINKING FOUNTAINS. COMPLY WITH FBC ACC 211.2 AND |
| | SECTION 602. |
| | B. ONE (1) SERVICE SINK |
| | |
| | 2. THE BSL-2 RESEARCH LABORATORY SUMMARY SUBMITTED IN |
| | SUPPORTING DOCUMENTS CALL OUT AN AUTOCLAVE. PER WPB FBC |
| | 107.2.1, PROVIDE MANUFACTURER?S |
| | SPECIFICATION/INSTALLATION MANUAL SHOWING COMPLIANCE |
| | WITH FBC PL 422.9 AND SHOW LOCATION ON THE PLANS. |
| | 3. THE BSL-2 RESEARCH LABORATORY SUMMARY SUBMITTED IN |
| | SUPPORTING DOCUMENTS CALL OUT AND SHOW TWO (2) |
| | EMERGENCY EYEWASH STATIONS. PER WPB FBC 107.2.1, |
| | PROVIDE MANUFACTURER?S SPECIFICATION/INSTALLATION |
| | MANUAL SHOWING COMPLIANCE WITH FBC PL 411.1 AND SHOW |
| | LOCATIONS ON THE PLANS. |
| | |
| | A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT |
| | THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A |
| | RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS |
| | FROM THE FIRST REVIEW. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS |
| | REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | |