| 2020-06-10 17:43:45 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20050766 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE BIO SAFETY PDF DOCUMENT IS A BLANK PAGE, PLEASE |
| | UPLOAD DOCUMENT. FBC FS 107.2.1 |
| | |
| | 2) SHEET M0.1: PLEASE PROVIDE OUTDOOR AIR CALCULATIONS |
| | INCLUDING THE SYSTEM VENTILATION EFFICIENCY. FBC |
| | M403.3.1.1.2.3.2 |
| | |
| | 3) PLEASE PROVIDE ENERGY CODE CALCULATIONS. FBC EC |
| | C403.2 |
| | |
| | 4) PLEASE PROVIDE A LIST OF HAZARDOUS MATERIALS WITH |
| | QUANTITIES OF EACH STORED FOR THIS FACILITY. FBC FS |
| | 107.2.1 |
| | |
| | 5) PLEASE PROVIDE SPEC SHEETS FOR ALL EQUIPMENT USED IN |
| | THESE AREAS. FBC FS 107.2.1 |
| | |
| | 6) ACCORDING TO THE A SHEETS THESE WALLS HAVE A FIRE |
| | RATING OF 1 HR. PLEASE SHOW ALL DUCT WORK PASSING |
| | THROUGH THESE WALLS ARE PROTECTED WITH THE REQUIRED FD. |
| | FBC M 607.5 |
| | |
| | 7) PLEASE SHOW HOW AHU-1 IS PROVIDING VENTILATION FOR |
| | THE AREA. SHOW DUCT WORK ON THE DRAWING. FBC FS 107.2.1 |
| | |
| | 8) PLEASE SHOW HOW THE HOODS LOCATED IN THE LABS ARE |
| | EXHAUSTING THE AIR AND SHOW THE EXHAUST TERMINATION |
| | LOCATION. FBC FS 107.2.1 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |