| 2020-05-29 11:13:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET A 1.11 - WITHIN THE LAB ROOM THERE ARE TWO |
| | HOODS INDICATED THAT ARE NOT ON THE MECHANICAL PLAN |
| | SHEETS. |
| | |
| | WHAT IS THE FUNCTION OF THESE HOODS AND DO THEY HAVE |
| | ANY VENTING/EXHAUSTED RELEATED FEATURES TO THEM? |
| | |
| | PLEASE PROVIDE DETAILS/SPEC SHEETS AND ADD THEM TO THE |
| | MECHANICAL PLANS IF APPLICABLE. |
| | |
| | |
| | |
| | 2) SHEET AO.14 - WITHIN THE DOOR SCHEDULE UNDER |
| | HARDWARE GROUP THERE ARE INDICATIONS OF TBD & N/A. |
| | |
| | ON REVIEW OF THE BACK UP INFORMATION LABORATORY SUMMARY |
| | THERE IS INDICATIONS OF: "LABORATORY FACILITIES |
| | (SECONDARY BARRIERS) # 1 LABORATORY DOORS SHOULD BE |
| | SELF-CLOSING AND HAVE LOCKS IN ACCORDANCE WITH THE |
| | COMPNAY PLOICIES." |
| | |
| | THERE ARE NO INDICATIONS OF SELF-CLOSERS WITHIN THE |
| | DOOR SCHEDULE. |
| | |
| | THERE ARE NO INDICATIONS OF DOO & LOCKS/LATCHING |
| | HARDWARE. |
| | |
| | PER NFPA 101 CH 7, MEANS OF EGRESS |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM |
| | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY |
| | TO DOOR |
| | LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO |
| | ELEVATED |
| | TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON |
| | LABORATORY |
| | FIRE TEST PROCEDURES. |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A |
| | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM |
| | THE EGRESS |
| | SIDE. |
| | |
| | PLEASE ENSURE COMPLIANCE. |
| | |
| | |
| | |
| | 3) ELECTRICAL SHEETS - FOR INFOMATIONAL PURPOSES ONLY |
| | |
| | THERE ARE NO INDICATIONS OF ACCESS CONTROL WITHIN THE |
| | PORJECT. |
| | |
| | SHOULD ACCESS CONTROL BE CONSIDERED, IT SHALL BE |
| | SUBMITTED UNDER SEPARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | PROVIDE AND APPLICABLE NOTE OF ACKNOWLEDGEMENT. |
| | |
| | PLEASE ENSURE COMPLINACE IF PROPOSED. |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |