Plan Review Notes
Plan Review Notes For Permit 20050766
Permit Number 20050766
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-05-29 11:13:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 1.11 - WITHIN THE LAB ROOM THERE ARE TWO
 HOODS INDICATED THAT ARE NOT ON THE MECHANICAL PLAN
 SHEETS.
  
 WHAT IS THE FUNCTION OF THESE HOODS AND DO THEY HAVE
 ANY VENTING/EXHAUSTED RELEATED FEATURES TO THEM?
  
 PLEASE PROVIDE DETAILS/SPEC SHEETS AND ADD THEM TO THE
 MECHANICAL PLANS IF APPLICABLE.
  
  
  
 2) SHEET AO.14 - WITHIN THE DOOR SCHEDULE UNDER
 HARDWARE GROUP THERE ARE INDICATIONS OF TBD & N/A.
  
 ON REVIEW OF THE BACK UP INFORMATION LABORATORY SUMMARY
 THERE IS INDICATIONS OF: "LABORATORY FACILITIES
 (SECONDARY BARRIERS) # 1 LABORATORY DOORS SHOULD BE
 SELF-CLOSING AND HAVE LOCKS IN ACCORDANCE WITH THE
 COMPNAY PLOICIES."
  
 THERE ARE NO INDICATIONS OF SELF-CLOSERS WITHIN THE
 DOOR SCHEDULE.
  
 THERE ARE NO INDICATIONS OF DOO & LOCKS/LATCHING
 HARDWARE.
  
 PER NFPA 101 CH 7, MEANS OF EGRESS
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
  
 PLEASE ENSURE COMPLIANCE.
  
  
  
 3) ELECTRICAL SHEETS - FOR INFOMATIONAL PURPOSES ONLY
  
 THERE ARE NO INDICATIONS OF ACCESS CONTROL WITHIN THE
 PORJECT.
  
 SHOULD ACCESS CONTROL BE CONSIDERED, IT SHALL BE
 SUBMITTED UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PROVIDE AND APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
 PLEASE ENSURE COMPLINACE IF PROPOSED.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  