| Plan Review Notes For Permit 20050763 |
| Permit Number |
20050763 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-07-17 16:49:28 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) SHOW LOCATION ON BUILDING OF ALL SERVICE DISCONNECTS | | | 230.72 | | | | | | 2) SUBMIT A LOAD CALCULATION DONE IN ACCORDANCE WITH | | | ARTICLE 220 OF THE NEC | | | | | | 3) VALUE JUST OF THE SERVICE IS LOW FOR INDUSTRY | | | STANDARDS. PLEASE ADJUST THE VALUE ACCORDING TO | | | INDUSTRY STANDARDS. (2450) | | | | | | 4) SHOW LOCATION OF PANEL IN BUILDING. | | | | | | 5) SUBMIT A PANEL SCHEDULE FOR NEW PANEL IN BUILDING | | | 215.5 | | | | | | 6) PLAN NEEDS TO BE SIGNED BY ENGINEER OR CONTRACTOR | | | WHO IS RESPONSIBLE FOR THE PLANS. |
|