Plan Review Notes
Plan Review Notes For Permit 20050763
Permit Number 20050763
Review Stop E
Sequence Number 2
Notes
Date Text
2020-07-17 16:49:28ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) SHOW LOCATION ON BUILDING OF ALL SERVICE DISCONNECTS
 230.72
  
 2) SUBMIT A LOAD CALCULATION DONE IN ACCORDANCE WITH
 ARTICLE 220 OF THE NEC
  
 3) VALUE JUST OF THE SERVICE IS LOW FOR INDUSTRY
 STANDARDS. PLEASE ADJUST THE VALUE ACCORDING TO
 INDUSTRY STANDARDS. (2450)
  
 4) SHOW LOCATION OF PANEL IN BUILDING.
  
 5) SUBMIT A PANEL SCHEDULE FOR NEW PANEL IN BUILDING
 215.5
  
 6) PLAN NEEDS TO BE SIGNED BY ENGINEER OR CONTRACTOR
 WHO IS RESPONSIBLE FOR THE PLANS.