2020-06-12 17:30:59BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- APPLICATION WAS SUBMITTED AS AN ELECTRICAL PERMIT
 ONLY FOR THE INSTALLATION OF SINGLE PHASE SERVICE METER
 & DISTRIBUTION PANEL INSTALL BRANCH CIRCUIT FOR RADIO.
 BASED ON THE INFORMATION SUBMITTED, IT LOOKS LIKE A
 COMMUNICATIONS PERMIT IS REQUIRED. SEE CITY ORDINANCE
 NO. 4774-18.
 NOTE: PLEASE SEE ZONING AND ENGINEERING COMMENTS.
  
 2- INFORMATION SUBMITTED INCLUDES THE INSTALLATION OF
 CONCRETE POLES. INFORMATION SUBMITTED FOR THE CONCRETE
 POLES IS INSUFFICIENT. ENGINEER OF RECORD TO PROVIDE
 COMPLETE DESIGN INFORMATION AS REQUIRED BY SEC.
 1603.1.4 FBC-BUILDING. ALSO, PROVIDE COMPLETE DETAILS
 AND SPECIFICATIONS FOR THE CONCRETE POLE.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE
 VALUATION AS REQUIRED, INCLUDING DESIGN PROFESSIONAL
 FEES.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,