| Notes |
| Date |
Text |
| 2020-10-25 13:16:17 | BUILDING PROVISO:THE SUBMITTED SKETCH SHOWS BOTH BOLTED | | | AND WELDED CONNECTIONS, PLEASE SHOW COMPLIANCE WITH | | | WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS | | | REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & | | | WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN | | | ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF | | | INSPECTION. THIRD PARTY CERTIFICATION WILL BE REQUIRED. | | | 2017 FBC-B 2204.1 WELDING | | | 1. WELD PROCEDURES SPECIFICATIONS | | | 2. QUALIFICATIONS OF WELDING PERSONAL | | | 2017 FBC-B 2204.2 BOLTING. | | | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED | | | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD | | | AT 561-805-6666. | | | WELDING CERTIFICATES WILL NEED TO BE ON THE JOBSITE AT | | | TIME OF INSPECTION SO THE INSPECTOR CAN BRING THEM INTO | | | THE CITY. | | | J. WITMER BUILDING PLANS EXAMINER |
|