Plan Review Notes
Plan Review Notes For Permit 20050739
Permit Number 20050739
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2020-08-10 13:23:46*******PREVIOUS FIRE COMMENTS WERE NOT SPECICALLY
 ADDRESSED***********
  
 PREVIOUS COMMENTS RESUBMITTED:
  
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED SHEET INDICATES THE "ALL" DECKS &
 BOLTS WITH NO INDICATION OF HOW MANY OR LEVELS.
  
 PLEASE PROVIDE A HORIZONTAL VIEW OF THE ENTIRE ESCAPE
 STAIR AND THE SPECIFIC LOCATIONS OF THE PROPOSED
 REPAIRS.
  
  
 2) THERE ARE NO INDICATIONS OF HOW LONG THIS PROPOSED
 REPAIR WILL TAKE AND WHAT MEASURES WILL BE PUT IN PLACE
 TO AVOID USE OF THE STAIR WHILE IT IS IN AN UNSAFE
 STATE.
  
 PER NFPA 101
  
 4.6.10 CONSTRUCTION, REPAIR, AND IMPROVEMENT
 OPERATIONS.
 4.6.10.1* BUILDINGS, OR PORTIONS OF BUILDINGS, SHALL BE
 PERMITTED TO
 BE OCCUPIED DURING CONSTRUCTION, REPAIR, ALTERATIONS,
 OR ADDITIONS
 ONLY WHERE REQUIRED MEANS OF EGRESS AND REQUIRED FIRE
 PROTECTION
 FEATURES ARE IN PLACE AND CONTINUOUSLY MAINTAINED FOR
 THE PORTION
 OCCUPIED OR WHERE ALTERNATIVE LIFE SAFETY MEASURES
 ACCEPTABLE TO
 THE AUTHORITY HAVING JURISDICTION ARE IN PLACE.
 4.6.10.2* IN BUILDINGS UNDER CONSTRUCTION, ADEQUATE
 ESCAPE
 FACILITIES SHALL BE MAINTAINED AT ALL TIMES FOR THE USE
 OF
 CONSTRUCTION WORKERS. ESCAPE FACILITIES SHALL CONSIST
 OF DOORS,
 WALKWAYS, STAIRS, RAMPS, FIRE ESCAPES, LADDERS, OR
 OTHER APPROVED
 MEANS OR DEVICES ARRANGED IN ACCORDANCE WITH THE
 GENERAL
 PRINCIPLES OF THE CODE INSOFAR AS THEY CAN REASONABLY
 BE APPLIED
 TO BUILDINGS UNDER CONSTRUCTION.
  
 PLEASE PROVIDE SPECIFIC DETAILS
  
  
  
 3) THERE IS NO INDICATIONS OF COMPLIANCE WITH NFPA 101,
 CH 7 MEANS OF EGRESS
  
 7.2.8.4 STAIR DETAILS. FIRE ESCAPE STAIRS SHALL COMPLY
 WITH THE
 REQUIREMENTS OF TABLE 7.2.8.4(A). REPLACEMENT OF FIRE
 ESCAPE
 STAIRS SHALL COMPLY WITH THE REQUIREMENTS OF TABLE
 7.2.8.4(B).
  
 7.2.8.6.2 THE AUTHORITY HAVING JURISDICTION SHALL BE
 PERMITTED TO
 APPROVE ANY EXISTING FIRE ESCAPE STAIR THAT HAS BEEN
 SHOWN BY LOAD
 TEST OR OTHER SATISFACTORY EVIDENCE TO HAVE ADEQUATE
 STRENGTH.
  
 PLEASE ENSURE COMPLAINCE WITH AN APPLICABLE NOTE AND
 PROVIDE DETAILS.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]