| 2020-08-10 13:23:46 | *******PREVIOUS FIRE COMMENTS WERE NOT SPECICALLY |
| | ADDRESSED*********** |
| | |
| | PREVIOUS COMMENTS RESUBMITTED: |
| | |
| | |
| | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THE SUBMITTED SHEET INDICATES THE "ALL" DECKS & |
| | BOLTS WITH NO INDICATION OF HOW MANY OR LEVELS. |
| | |
| | PLEASE PROVIDE A HORIZONTAL VIEW OF THE ENTIRE ESCAPE |
| | STAIR AND THE SPECIFIC LOCATIONS OF THE PROPOSED |
| | REPAIRS. |
| | |
| | |
| | 2) THERE ARE NO INDICATIONS OF HOW LONG THIS PROPOSED |
| | REPAIR WILL TAKE AND WHAT MEASURES WILL BE PUT IN PLACE |
| | TO AVOID USE OF THE STAIR WHILE IT IS IN AN UNSAFE |
| | STATE. |
| | |
| | PER NFPA 101 |
| | |
| | 4.6.10 CONSTRUCTION, REPAIR, AND IMPROVEMENT |
| | OPERATIONS. |
| | 4.6.10.1* BUILDINGS, OR PORTIONS OF BUILDINGS, SHALL BE |
| | PERMITTED TO |
| | BE OCCUPIED DURING CONSTRUCTION, REPAIR, ALTERATIONS, |
| | OR ADDITIONS |
| | ONLY WHERE REQUIRED MEANS OF EGRESS AND REQUIRED FIRE |
| | PROTECTION |
| | FEATURES ARE IN PLACE AND CONTINUOUSLY MAINTAINED FOR |
| | THE PORTION |
| | OCCUPIED OR WHERE ALTERNATIVE LIFE SAFETY MEASURES |
| | ACCEPTABLE TO |
| | THE AUTHORITY HAVING JURISDICTION ARE IN PLACE. |
| | 4.6.10.2* IN BUILDINGS UNDER CONSTRUCTION, ADEQUATE |
| | ESCAPE |
| | FACILITIES SHALL BE MAINTAINED AT ALL TIMES FOR THE USE |
| | OF |
| | CONSTRUCTION WORKERS. ESCAPE FACILITIES SHALL CONSIST |
| | OF DOORS, |
| | WALKWAYS, STAIRS, RAMPS, FIRE ESCAPES, LADDERS, OR |
| | OTHER APPROVED |
| | MEANS OR DEVICES ARRANGED IN ACCORDANCE WITH THE |
| | GENERAL |
| | PRINCIPLES OF THE CODE INSOFAR AS THEY CAN REASONABLY |
| | BE APPLIED |
| | TO BUILDINGS UNDER CONSTRUCTION. |
| | |
| | PLEASE PROVIDE SPECIFIC DETAILS |
| | |
| | |
| | |
| | 3) THERE IS NO INDICATIONS OF COMPLIANCE WITH NFPA 101, |
| | CH 7 MEANS OF EGRESS |
| | |
| | 7.2.8.4 STAIR DETAILS. FIRE ESCAPE STAIRS SHALL COMPLY |
| | WITH THE |
| | REQUIREMENTS OF TABLE 7.2.8.4(A). REPLACEMENT OF FIRE |
| | ESCAPE |
| | STAIRS SHALL COMPLY WITH THE REQUIREMENTS OF TABLE |
| | 7.2.8.4(B). |
| | |
| | 7.2.8.6.2 THE AUTHORITY HAVING JURISDICTION SHALL BE |
| | PERMITTED TO |
| | APPROVE ANY EXISTING FIRE ESCAPE STAIR THAT HAS BEEN |
| | SHOWN BY LOAD |
| | TEST OR OTHER SATISFACTORY EVIDENCE TO HAVE ADEQUATE |
| | STRENGTH. |
| | |
| | PLEASE ENSURE COMPLAINCE WITH AN APPLICABLE NOTE AND |
| | PROVIDE DETAILS. |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |