| 2020-06-21 15:51:42 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20050739 |
| | ADD: 120 S. OLIVE AVE. |
| | CONT: PETTERSON CONSTTRUCTION GROUP |
| | TEL: 954-649-5986 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SUN. JUNE 21ST/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) THE SUBMITTED VALUE FOR THE PROPOSED PROJECT IS LOW |
| | FOR THE FABRICATION AND INSTALLATION OF THIS PROJECT |
| | AND REQUIRED ENGINEERING. |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 109.3* |
| | BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 2) THE SUBMITTED SKETCH OF WHAT APPEARS TO BE A |
| | MID-LANDING, IS THE ONLY DOCUMENT SUBMITTED FOR PLANS. |
| | THERE IS NO SITE PLAN SHOWING THE LOCATION OF THE FIRE |
| | ESCAPE, DISTANCE BETWEEN BUILDINGS, NOR IS THERE AN |
| | ELEVATION VIEW SHOWING THE LOCATION OF THIS MID-LANDING |
| | HEIGHT ABOVE GRADE OR CLEARANCE AT THE BOTTOM OF THE |
| | WALL BRACE LOCATED BELOW THE LANDING. THE PLANS ARE |
| | ALSO SILENT AS TO WHAT ANCHORS ARE GOING TO BE USED IN |
| | THE INSTALLATION OR IF THE WALL IS TERRA-COTTA WALL |
| | SYSTEM COMMONLY USED IN THAT TIME PERIOD OR OTHER |
| | MATERIAL? THERE IS NO MENTION OF THE EXISTING GUARDRAIL |
| | AT THE PROPOSED LANDING? THE PROPOSED DESIGNER ALSO HAS |
| | NOT INCLUDED ANY CALCULATIONS FOR THE LOADS TO BE |
| | CARRIED BY THE NON-CEMETERY LOADING OF THE WALL |
| | BRACING. CERTIFICATION BY CONTRACTORS CAN ONLY OCCUR ON |
| | DRAWINGS FOR ONE AND TWO FAMILY DWELLINGS AND INTERIOR |
| | WORK THAT DOES NOT INCLUDE STRUCTURAL ENGINEERING. |
| | 107.4.3.2 CERTIFICATION BY CONTRACTORS AND F. S. |
| | 471.003?QUALIFICATIONS FOR PRACTICE ENGINEERING ;(1) NO |
| | PERSON OTHER THAN A DULY LICENSED ENGINEER SHALL |
| | PRACTICE ENGINEERING. |
| | |
| | 3) THE SUBMITTED SKETCH SHOWS BOTH BOLTED AND WELDED |
| | CONNECTIONS, PLEASE SHOW COMPLIANCE WITH WELDED OR |
| | BOLTED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO |
| | PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR |
| | PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH |
| | THE REFERENCED STANDARDS AT TIME OF INSPECTION. THIRD |
| | PARTY CERTIFICATION WILL BE REQUIRED. |
| | 2017 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| | AT 561-805-6666. |
| | |
| | 4) THE SUBMITTED SKETCH WILL NEED TO SHOW COMPLIANCE |
| | WITH THE CALCULATION FOR THE FIRE ESCAPE AND LIVE LOADS |
| | FOR 100 PSF 2017 FBC-B TABLE 1607.1(13) FIRE ESCAPES. |
| | |
| | 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |