| 2020-06-03 08:19:16 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT -20050699 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) MASTER PERMIT 19110910 SHEET M-1 SPECS L2 AND L3 |
| | LOUVERS IN THE GENERATOR ROOM TO BE 80X48. SHEET E10 |
| | ?GENERATOR ROOM DETAIL? CALLS FOR THE EXHAUST LOUVER TO |
| | BE 108X108. PLEASE CLARIFY THIS FOR BOTH PROJECTS. FBC |
| | FS 107.2.1 |
| | |
| | 2) PLEASE PROVIDE CALCULATIONS FOR THE COMBUSTION AIR |
| | NEEDED FOR THIS GENERATOR AND THE MINIMUM SIZE OUTDOOR |
| | OPENING. FBC FG 304.6 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |