| 2020-06-23 14:09:05 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20050685 |
| | ADD: 2995 45TH ST. / RACE TRAC |
| | CONT: ATLAS SIGN HOLDINGS |
| | TEL: 561-863-6659 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | PERMIT FOR (2) NON-ILLUMINATED AWNINGS / VALUE OF |
| | $11,937.00. AWNINGS (AH) & (AI). |
| | |
| | 1ST REVIEW |
| | DATE: TUES. JUNE 23RD/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) THERE ARE SHEETS INCLUDED IN THIS PERMIT PACKAGE |
| | THAT HAVE NOTHING TO DO WITH THE 2 NON-ILLUMINATED |
| | AWNINGS, THEY NEED TO BE REMOVED OR BE MARKED VOID NOT |
| | PART OF THIS PERMIT. 107.2.1.2 ADDITIONAL INFORMATION |
| | IS REQUIRED. |
| | |
| | 2) SHEETS S-5 FOR AWNING A-I & SHEET S-6 FOR AWNING A-J |
| | BOTH SHOW THE STRUCTURAL FRAMEWORK OF THE AWNING BUT |
| | NOTHING IS INDICATED AS TO THE MATERIAL COVERING IS TO |
| | BE MADE FROM? FOR THIS REVIEW PURPOSE IT IS SUPPOSED TO |
| | BE A CLOTH MATERIAL. 2017 FBC-B SECTION 3105.3.4.1. |
| | MATERIALS. WHEN FABRIC IS USED TO COVER AWNINGS OR |
| | FABRIC OVER COVERED FRAMES SHALL MEET THE FLAME |
| | PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 OR HAVE A |
| | FLAME SPREAD INDEX NOT GREATER THAN 25 WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E-84 OR UL 723. |
| | |
| | 3) BOTH SHEETS S5 & S6 BOTH GIVE THE WIND DESIGN |
| | CRITERIA OF 170 VULT EXPOSURE C BUT THE PLANS DO NOT |
| | STATE IF THIS IS FOR THE BUILDING OR AWNINGS. PLEASE |
| | REVIEW THE 2 CODE SECTIONS BELOW FOR BREAKAWAY FABRIC |
| | OR PERMANENT NON-REMOVALABLE FABRIC. |
| | |
| | RIGID AWNINGS. BREAK AWAY FABRIC. FBC-B |
| | 3105.4.2.1.DESIGN. THE WIND DESIGN LOADS FOR ANY FABRIC |
| | OR MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK |
| | REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND |
| | VELOCITIES OF 75 MPH, SHALL BE BASED ON THE FOLLOWING |
| | CRITERIA: |
| | 1) MINIMUM WIND SPEED OF 105 MPH |
| | 2) EXPOSURES B, C, OR D AS DEFINED IN CHAPTER 16. |
| | |
| | RIGID AWNING. PERMANENT OR NON-REMOVABLE FABRIC. FBC-B |
| | 3105.4.2.2. THE WIND DESIGN LOADS FOR ANY FABRIC OR |
| | MEMBRANE COVERED STRUCTURE DESIGNED WITH A PERMANENT OR |
| | NON-REMOVABLE FABRIC OR MEMBRANE, SHALL BE BASED ON THE |
| | FOLLOWING CRITERIA: |
| | 1) MINIMUM WIND SPEED VELOCITY AS REQUIRED IN CHAPTER |
| | 16 USING FIGURE 1609.3(3) 150 VULT, CATEGORY 1 |
| | BUILDINGS. |
| | 2) EXPOSURES B, C, OR D AS DEFINED IN CHAPTER 16. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |