Plan Review Notes
Plan Review Notes For Permit 20050672
Permit Number 20050672
Review Stop P
Sequence Number 2
Notes
Date Text
2020-08-03 14:40:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 1. PLEASE NOTE; THE SCOPE OF WORK NOTED ON PLAN SHEET
 A0.01 INDICATES A MUCH LARGER SCOPE INCLUDING BUT NOT
 LIMITED TO ELECTRICAL AND MILLWORK THAN IS INDICATED IN
 THE CONTRACT OR ON THE PERMIT APPLICATIONS. THIS
 IMPACTS THE PERMIT FEES AND NEEDS TO BE ADDRESSED.
  
 2. SERVICE VALVE
 NOTE THAT PER FBC PL 606.1, A DEDICATED FULL-OPEN
 SERVICE VALVES SHALL BE INSTALLED ON THE ENTRANCE TO
 EVERY WATER SUPPLY PIPE TO A DWELLING UNIT. SERVICE
 VALVE AT FIRST FLOOR UNITS IN THE WATER RISER DIAGRAM
 APPEARS TO SHUT DOWN THE ENTIRE RISER. PER WPB FBC
 107.2.1, PROVIDE CLARIFICATION.
 SERVICE VALVE SHALL BE ACCESSIBLE PER FBC PL 606.3. PER
 WPB FBC 107.2.1, PROVIDE NOTE THAT THE SERVICE VALVE
 SHALL BE ACCESSIBLE PER FBC PL 606.3.
  
 3. SHUT OFF VALVE FOR WATER HEATER
 SHUT OFF VALVES FOR THE WATER HEATER SHALL BE
 ACCESSIBLE PER FBC PL 606.3 AND 503.1. WATER RISER
 DIAGRAM SEEMS TO INDICATE A SHUT OFF VALVE (BALL
 VALVE?) IN THE COLD WATER LINE GOING TO THE WATER
 HEATER AS WELL AS A SEPARATE COLD WATER AND HOT WATER
 SHUT OFF VALVE AT THE WATER HEATER WHICH APPEAR TO OF
 NO USE AS THE KITCHEN MILLWORK WOULD HAVE TO BE
 DISASSEMBLED AND/OR THE RANGE WOULD HAVE TO BE REMOVED
 IN ORDER TO ACCESS. PER WPB FBC 107.2.1, CLARIFY.
 PER WPB FBC 107.2.1, PROVIDE NOTE THAT THE SHUT OFF
 VALVE FOR WATER HEATER SHALL BE ACCESSIBLE.
  
 4. REPLACEMENT WATER HEATER
 PER WPB FBC 107.2.1, SPECIFY THE REPLACEMENT WATER
 HEATER. PROVIDE MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUAL INCLUSIVE OF
 ELECTRICAL CHARACTERISTICS AND WATER CONNECTIONS.
 PROVIDE A THERMAL EXPANSION RELIEF VALVE INTO THE COLD
 WATER SERVICE TO THE BUILDING BETWEEN THE SERVICE VALVE
 AND THE BUILDING OR AT THE DOWNSTREAM SIDE OF THE
 BACKFLOW PREVENTER.
 PER WPB FBC 107.2.1, PROVIDE NOTE "THE T & P RELIEF
 LINE/PAN DRAIN TERMINATION POINT ON THE BUILDING
 EXTERIOR FOR EACH WATER HEATER SHALL BE LOCATED AND
 MADE VISIBLE AND TESTED TO SHOW THAT THEY ARE CLEAR OF
 ANY OBSTRUCTION TO THE SATISFACTION OF THE PLUMBING
 INSPECTOR AT OR PRIOR TO FINAL INSPECTION".
  
  
 5. PLAN SHEET P4, SPECIFICATION NOTE 4, SPECIFICALLY
 PROHIBITS THE INSTALLATION OF POTABLE WATER BELOW ANY
 FLOOR ON GRADE OR FILL. PLAN SHEETS 2 AND 3 CLEARLY
 SHOW POTABLE WATER INSTALLED UNDER THE FLOOR ON GRADE
 OR FILL. PER WPB FBC 107.2.1, CLARIFY.
  
 6. CONTRACT IN SUPPORTING DOCUMENTS PROVIDES FOR
 INSTALLATION OF NEW ACRYLIC SHOWER ENCLOSURE. THERE IS
 NO MENTION OF THIS ON THE PERMIT APPLICATION OR ON THE
 PLANS. PER WPB FBC 107.2, CLARIFY. IF THIS IS PART OF
 THE SCOPE OF WORK, THEN INDICATE ON THE PLANS AND
 PROVIDE MANUFACTURER'S SPECIFICATION/INSTALLATION
 MANUAL.
  
 7. PLAN SHEET A2.01 NOTE REFERS TO A8.01 FOR PLUMBING
 REQUIREMENTS. THE ONLY REFERENCE TO PLUMBING THAT I SEE
 ON A8.01 IS THE VANITY TOP DETAIL SHOWING WATER CLOSET
 AND LAVATORY PLACEMENT. ADDITIONALLY PLAN SHEET A0.01
 SCOPE OF WORK CALLS FOR REMOVE/REPLACE ALL PLUMBING
 FIXTURES THROUGHOUT EACH UNIT AS WELL AS OTHER ITEMS
 NOT NOTED CONTRACT IN SUPPORTING DOCUMENTS AND/OR IN
 THE PERMIT APPLICATIONS. ARE THE PLUMBING FIXTURES
 BEING REPLACED BEING REPLACED? PER WPB FBC 107.2.1,
 CLARIFY.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  