| 2020-07-22 11:52:03 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20050672 |
| | ADD: 1320 ALPHA ST. |
| | CONT: GEN-X-CONSTRUCTION |
| | TEL: 561-963-4490 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: WED. JULY 22ND/2020 |
| | ACTION: DENIED |
| | |
| | 1) SEMI-COMPLIED. SHEET A8.02 DOES SHOW THE SLAB REPAIR |
| | AND SHEET A8.01 SHOWS THE ONE HOUR FIRE RATING FOR |
| | BETWEEN UNITS WITH FIRE X DRYWALL BUT THERE IS NO |
| | MENTION IN THIS DETAIL HOW COMPLIANCE IS TO BE MET IN |
| | THE SHOWER WHERE YOU WILL ALSO NEED TO SHOW COMPLIANCE |
| | WITH SECTION: 2509.2 BASE FOR TILE IN THE 2017 FBC-B. |
| | MATERIALS USED AS A BASE FOR WALL TILE IN TUB AND |
| | SHOWER AREAS AND WALLS AND CEILING PANELS IN SHOWER |
| | AREAS SHALL BE OF MATERIALS LISTED IN TABLE 2509.2 AND |
| | INSTALLED IN ACCORDANCE WITH MANUFACTURER?S |
| | RECOMMENDATIONS. WATER RESISTANT GYPSUM BACKING BOARD |
| | SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET |
| | COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH |
| | GA-216 OR ASTM C840 AND THE MANUFACTURER'S |
| | RECOMMENDATIONS. |
| | |
| | 2) SEMI- COMPLIED SEE COMMENT # 1. PLEASE PROVIDE IN |
| | THE FLOOR PLAN, THE R2 UNITS THAT ARE BACK TO BACK AND |
| | HAVE REPLACEMENT PLUMBING IN THESE WALLS. SHOW HOW |
| | CONFORMANCE WITH THE 1 HOUR FIRE SEPARATION (FIRE |
| | PARTITIONS) REQUIRED BY SECTION708.1 AND 420 FBC-B AND |
| | IN CONFORMANCE WITH THE FIRE RESISTANCE RATING OF |
| | 708.3. |
| | . |
| | 3) COMPLIED. PLUMBING THAT IS WITHIN THE 1 HOUR TENANT |
| | SEPARATION WALL AND EXTENDS THROUGH THE WALL MEMBRANE |
| | WILL NEED TO PROVIDE COMPLIANCE WITH 714.3.2 COMPLYING |
| | WITH 714.3.1.2 THROUGH- PENETRATION FIRESTOP SYSTEM. |
| | |
| | 4) COMPLIED. IT IS UNKNOWN IF THIS IS A MULTIPLE STORY |
| | APARTMENT COMPLEX, THIS INFORMATION WAS NOT GIVEN. IF |
| | SO COMPLIANCE WITH 714.4 HORIZONTAL ASSEMBLIES AND |
| | 714.4.1 THROUGH PENETRATIONS AND 714.4.1.2. HORIZONTAL |
| | THROUGH-PENETRATIONS FIRESTOP ASSEMBLIES WILL NEED TO |
| | SHOW COMPLIANCE. |
| | |
| | 5) COMPLIED. THE BUILDING PLANS WILL NEED TO COMPLY |
| | WITH THE, 107.2.1.3. QUALITY OF PLANS. BUILDING PLANS |
| | SHALL BE DRAWN TO A 1/8TH INCH SCALE ON SUBSTANTIAL |
| | PAPER OR OTHER ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL |
| | MAY ESTABLISH THROUGH DEPARTMENT POLICY OTHER STANDARDS |
| | FOR THE PLANS AND SPECIFICATIONS IN ORDER TO PROVIDE |
| | CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY |
| | MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, |
| | CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORD |
| | MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH |
| | THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. |
| | |
| | 6) 2ND REQUEST. THE SUBMITTED PLANS BY ARCHITECT HAROLD |
| | TUTTLE IT WOULD APPEAR TO BE PAPER PLANS AND WOULD NEED |
| | TO BE UPLOADED WITH DIGITAL SIGNATURES. ARCHITECTS: |
| | FLORIDA ADMINISTRATIVE CODE 61G1-16.005. PROCEDURES FOR |
| | DIGITALLY SIGNING AND SEALING AND FOR ELECTRONICALLY |
| | TRANSMITTING PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| | DOCUMENTS. |
| | |
| | 1ST ROUND OF COMMENTS. CERTIFICATION BY CONTRACTOR. |
| | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE |
| | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| | (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT |
| | WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE |
| | CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. |
| | THE CONTRACTOR (QUALIFIER) THAT CREATED / DRAWN THE SET |
| | OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR |
| | OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME |
| | AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN |
| | AND PLANS DRAWN. FOR EACH TRADE THE CONTRACTOR |
| | RESPONSIBLE FOR THE DESIGN UNDER THE TRADE LICENSED IN |
| | MUST PRINT THEIR NAME, SIGN THEIR NAME AND LICENSE |
| | NUMBER, NOTE THESE PLANS APPEAR TO BE DRAWN BY ONE |
| | INDUVIAL, THEY WOULD HAVE TO BE LICENSED AS A BUILDING, |
| | ELECTRICAL AND PLUMBING CONTRACTOR TO SUBMIT ALL THESE |
| | TRADES UNDER ONE SHEET. |
| | |
| | 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME IF YOU WOULD LIKE |
| | TO CONTACT ME, MY CELL NUMBER IS 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |