| Date |
Text |
| 2020-07-07 08:20:45 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20050672 1320 ALPHA ST |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. PER WPB FBC 107.2.1, SUBMIT A FIRST AND SECOND FLOOR |
| | PLAN OF BUILDING INDICATING ALL APARTMENTS AND LAUNDRY |
| | ROOM, ETC. SHOW PLUMBING ROUTING AND ALL PLUMBING |
| | FIXTURES; INDICATE ALL TIE IN POINTS. CLEARLY INDICATE |
| | ON PLAN THAT CONFIGURATION OF REPLACEMENT PIPING IS |
| | UNCHANGED. |
| | NOTE: THE BUILDING PLANS WILL NEED TO COMPLY WITH THE, |
| | 107.2.1.3. QUALITY OF PLANS. BUILDING PLANS SHALL BE |
| | DRAWN TO A 1/8TH INCH SCALE ON SUBSTANTIAL PAPER OR |
| | OTHER ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL MAY |
| | ESTABLISH THROUGH DEPARTMENT POLICY OTHER STANDARDS FOR |
| | THE PLANS AND SPECIFICATIONS IN ORDER TO PROVIDE |
| | CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY |
| | MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, |
| | CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORD |
| | MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH |
| | THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. A PLAN OF |
| | RECORD IS AVAILABLE FROM THE WPB BUILDING DEPARTMENT BY |
| | CONTACTING CRAIG MCPHERSON AT 561-805-6684; EMAIL |
| | [email protected]. |
| | |
| | 2. CERTIFICATION BY CONTRACTOR. 107.3.4.3 CERTIFICATION |
| | BY CONTRACTOR. PLEASE NOTE THE EXCEPTION TO ENGINEERED |
| | PLANS UNDER 471.003(H) ELECTRICAL/ PLUMBING/MECHANICAL, |
| | 481.229(1)(C) (BUILDING) REQUIRES THE CONTRACTOR FOR |
| | THAT TRADE THAT WILL BE LICENSED IN THAT TRADE, WILL |
| | ALSO BE THE CONTRACTOR THAT DESIGNS THE SYSTEM UNDER |
| | THAT TRADE. THE CONTRACTOR (QUALIFIER) THAT CREATED / |
| | DRAWN THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES |
| | AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME, |
| | SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE |
| | LICENSED IN AND PLANS DRAWN. FOR EACH TRADE THE |
| | CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER THE TRADE |
| | LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR NAME AND |
| | LICENSE NUMBER, NOTE THESE PLANS APPEAR TO BE DRAWN BY |
| | ONE INDIVIDUAL; EACH DISCIPLINE SUBMITTED SHALL BE BY A |
| | LICENSED CONTRACTOR IN THAT DISCIPLINE. |
| | |
| | 3. PER WPB FBC 107.2.1, SPECIFY ON THE PLANS MATERIAL |
| | TYPE FOR SANITARY PIPING. |
| | |
| | 4. PROVIDE SLAB REPAIR DETAIL SHOWING COMPLIANCE WITH |
| | FBC SECTIONS: |
| | 1A) VAPOR BARRIER: 1805.2.1/ 1907.1. FLOORS. |
| | 1B) TERMITE TREATMENT 1816.1.2 & 1816.1.3. |
| | 1C) RE-INFORCEMENT OF SLAB WHERE REMOVED. 1907.2(2). |
| | |
| | 5. PER WPB FBC 107.2.1, PROVIDE DETAILS FOR HORIZONTAL |
| | AND VERTICAL PIPE PENETRATIONS OF RATED WALLS AND |
| | FLOORS SHOWING COMPLIANCE WITH FBC CHAPTER 7. |
| | |
| | 6. A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISED AT |
| | THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A |
| | RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS |
| | FROM THE FIRST REVIEW |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS |
| | REQUIRED BY FAC AND FS. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | |
| | 20050672 1320 ALPHA ST |
| | |
| | |
| | |
| | |