| 2020-05-29 16:51:21 | PLAN REVIEW - ELECTRICAL |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE AN ELECTRICAL PLAN. IDENTIFY LOCATION OF ALL |
| | NEW DEVICES. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS |
| | |
| | 2. PROVIDE NEW LOAD CALC'S. SHOW OVERCURRENT PROTECTION |
| | AND CABLE SIZES. SPECIFY WHAT HP MOTOR WILL BE |
| | INSTALLED. |
| | PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING |
| | AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS |
| | ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 |
| | |
| | 3. PROVIDE NEW PANEL SCHEDULE. |
| | PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, |
| | 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 |
| | |
| | 4. PROVIDE LOW VOLTAGE DETAILS. |
| | PROVIDE DATA SPECIFICATION SHEET SUBMITTALS FOR ANY LOW |
| | VOLTAGE SYSTEMS PRESENT. FBC 105.1, 107.2.1 |
| | |
| | |
| | |
| | |