| Plan Review Notes For Permit 20050648 |
| Permit Number |
20050648 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-05-22 14:54:12 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) PROVIDE A ROOF DIAGRAM, WITH DIMENSIONS OF EACH ROOF | | | AREA, MEAN ROOF HEIGHT AND ROOF SLOPES SPECIFIED. FBC | | | 107.1.2 | | | | | | 2) THE PRODUCT APPROVAL FOR THE FLAT ROOF FL #2533 - | | | R23 HAS A MAXIMUM DESIGN PRESSURE OF -80 PSF. THE | | | REQUIRED ROOF PRESSURES FOR 170 MPH ESPOSURE C WITH A | | | 15' MEAN ROOF REIGHT IS -95.7 IN ROOF ZONE 3. SUBMIT | | | SIGNED AND SEALED ENHANCED FASTENING CALCULATIONS AS | | | REQUIRED BY LIMITATION NUMBER 5.7 ON SHEET 5 OF 6 OF | | | THE PRODUCT APPROVAL. FBC 1507 & FBC 107.3.4 | | | | | | 3) LIMITATION #5.9 ON SHEET 5 OF 6 OF PRODUCT APPROVAL | | | FL #2533 - R23 REQUIRES FASTENER WITHDRAWL TESTING FOR | | | MECHANICALLY FASTENED MEMBRANE OVER EXISTING WOOD | | | DECKS. SUBMIT TEST REPORTS. FBC 107.2.1 |
|