| 2020-06-19 14:15:12 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. THERE ARE DISCREPANCIES ON SEVERAL SHEETS. E-601 AND |
| | E-604 SHOW THERE IS ONE METER EXISTING, WHILE E-603 AND |
| | E-606 SHOW THERE ARE TWO METERS. PROVIDE CLARIFICATION |
| | AND CORRECTIONS AS NEEDED. WPB FBC 107.2.1 |
| | 2. PROVIDE WIRE SIZES FOR ALL NEW WIRING SHOWN ON PLAN. |
| | NEC 215.5, 310.15(B)(16); WPB FBC 107.2.1 |
| | 3. WHAT TYPE OF VOLTAGE (AC OR DC) WILL BE RUN BETWEEN |
| | THE BUILDINGS IN THE TRENCH, WHAT TYPE OF CONDUIT WILL |
| | BE USED? WHERE IS THE OVERCURRENT PROTECTION FOR THESE |
| | CONDUCTORS? PROVIDE CLARIFICAITON. WPB FBC 107.2.1; NEC |
| | 690.9, 690.10, 690.31(G). |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |