| Plan Review Notes For Permit 20050553 |
| Permit Number |
20050553 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-06-29 11:42:12 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: THE COMMENTS FROM | | | THE FIRST REVIEW HAVE NOT BEEN ADDRESSED. | | | | | | 1) THE LATERAL WIND PRESSURE THAT IS MARKED ON THE | | | GENERATOR PAD DRAWING FOR RG038 OF 36 PSF IS NOT | | | ADEQUATE FOR THIS PROJECT. RISK CATEGORY II IN EXPOSURE | | | C IN PALM BEACH COUNTY REQUIRES 41.65 PSF. FBC R301 | | | | | | 2) THE ENGINEER'S DIGITAL SIGNATURE AND SEAL IS | | | REQUIRED ON THE GENERATOR PAD DRAWING. FS 471 & FAC | | | 61G15 |
|