2020-06-29 11:42:12PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW: THE COMMENTS FROM
 THE FIRST REVIEW HAVE NOT BEEN ADDRESSED.
  
 1) THE LATERAL WIND PRESSURE THAT IS MARKED ON THE
 GENERATOR PAD DRAWING FOR RG038 OF 36 PSF IS NOT
 ADEQUATE FOR THIS PROJECT. RISK CATEGORY II IN EXPOSURE
 C IN PALM BEACH COUNTY REQUIRES 41.65 PSF. FBC R301
  
 2) THE ENGINEER'S DIGITAL SIGNATURE AND SEAL IS
 REQUIRED ON THE GENERATOR PAD DRAWING. FS 471 & FAC
 61G15