Plan Review Notes
Plan Review Notes For Permit 20050553
Permit Number 20050553
Review Stop B
Sequence Number 1
Notes
Date Text
2020-06-10 11:35:05PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE LATERAL WIND PRESSURE THAT IS MARKED ON THE
 GENERATOR PAD DRAWING FOR RG038 OF 36 PSF IS NOT
 ADEQUATE FOR THIS PROJECT. RISK CATEGORY II IN EXPOSURE
 C IN PALM BEACH COUNTY REQUIRES 41.65 PSF. FBC R301
  
 2) THE ENGINEER'S DIGITAL SIGNATURE AND SEAL IS
 REQUIRED ON THE GENERATOR PAD DRAWING. FS 471 & FAC
 61G15