| Plan Review Notes For Permit 20050544 |
| Permit Number |
20050544 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-05-21 09:55:57 | ROOFING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT | | | APPROVAL REQUIRES ADDITIONAL SIGNED AND SEALED | | | ATTACHMENT DETAILS AND FASTENER TESTING FROM AN | | | ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH | | | REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE | | | PRODUCT APPROVAL (-60) - SEE NOTE NUMBER 9 (ADDITIONAL | | | ATTACHMENTS) AND NOTE NUMBER 11 (FASTENER TESTING) ON | | | THE PRODUCT APPROVAL. SIGNED AND SEALED DRAWINGS OR | | | DOCUMENTS WILL NEED TO BE DIGITALLY SIGNED AND SEALED | | | TO BE USED IN ELECTRONIC PLAN REVIEW. SHOW THE WIND | | | DESIGN DATA USED PER 2017 FBC AND ASCE 7-10 - WIND | | | SPEED - EXPOSURE - RISK CATEGORY - ETC. | | | | | | FYI = ENGINEER CANNOT SELF-CERTIFY THE DIGITAL | | | SIGNATURE | | | 668.003(2) AND (3), F.S. | | | (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL | | | SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING | | | PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL HAVE | | | THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION | | | AUTHORITY. | | | | | | |
|