| 2020-08-11 11:57:20 | 2ND REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20050532 |
| | 8/11/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE REVISED GAS ISOMETRIC IS LACKING THESE DETAILS |
| | AND INFORMATION. PLEASE REVISE PER THE NOTES BELOW: |
| | |
| | A) SHOW HOW THE GAS PIPE SUPPLYING THE APPLIANCES IN |
| | THE HOUSE IS CONNECTING TO THE METER. INDICATE THE TYPE |
| | AND SIZE OF SUPPLY PIPE, AND TOTAL LENGTH OF THE RUN TO |
| | THE MOST REMOTE OUTLET.- SECTION G2413.3 FBC RES. |
| | B) PROVIDE THE INDIVIDUAL AND TOTAL LOADS OF ALL |
| | GAS-FIRED APPLIANCES AND EQUIPMENT BEING SUPPLIED BY |
| | THE METER AND METER'S TOTAL CAPACITY AS NOTED IN THE |
| | SUBMITTED LETTER- SECTION G2413.2 FBC RES. |
| | C) INDICATE WHICH PIPE SIZING TABLE WAS USED FOR THE |
| | NEW PE LINE TO THE POOL HEATER- SECTION G2413.4 FBC |
| | RES. |
| | 2) AS PREVIOUSLY REQUESTED, SUBMIT SPECS FOR THE POOL |
| | WATER HEATER INDICATING THE BTUH LOAD AND REQUIRED GAS |
| | PRESSURE- G2441.1 FBC RES. PLEASE NOTE THE WORD ?POOL? |
| | WAS ADDED FOR CLARITY. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |