| 2020-06-17 12:47:08 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20050502 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THIS IS AN EXISTING GAS METER, I CANNOT REVIEW THIS |
| | PROJECT UNTIL THE ENTIRE GAS SYSTEM HAS BEEN SUBMITTED. |
| | PLEASE SUBMIT A LEGIBLE DRAWING SHOWING GAS PRESSURE OF |
| | THE CURRENT EXISTING GAS SYSTEM, A HOUSE LAYOUT WITH |
| | THE GAS LINES SHOWN. PLEASE INCLUDE ALL REGULATORS AND |
| | SHUT OFF VALVES. PROVIDE THE SPECS FOR THE REGULATORS |
| | USED. PROVIDE PIPE SIZES, TYPE OF MATERIAL USED. PLEASE |
| | ALSO INCLUDE THE GAS TABLE NUMBER USED FOR EACH TYPE OF |
| | PIPING IN THIS SYSTEM. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |