| 2020-05-29 15:42:49 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| | SHALL COMPLY WITH THE MATERIALS AND METHODS |
| | REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | |
| | 1- THE WIND EXPOSURE CATEGORY SPECIFIED UNDER SITE |
| | DETAILS ON SHEET PV-1 IS INCORRECT. . ACCORDING TO SEC. |
| | R301.2.1.4 FBC-RESIDENTIAL THIS BUILDINGS LOCATED |
| | IN-EXPOSURE "C" NOT "B". REVISE AS REQUIRED. |
| | |
| | 2- INFORMATION SPECIFIED ON PAGE 1 OF THE "QDESIGN" |
| | DRAWINGS SUBMITTED IS INCORRECT: |
| | A) THE WIND EXPOSURE CATEGORY IS "C" NOT "B". SEC. |
| | R301.2.1.4 FBC-RESIDENTIAL. REVISE "SPECIFICATIONS" |
| | INFORMATION AS REQUIRED. |
| | |
| | B) THE ROOFING TYPE FOR THIS HOUSE IS CONCRETE TILE NOT |
| | SHINGLES. SEC. 107.2.1 CITY AMENDMENTS. REVISE |
| | "STRUCTURAL" INFORMATION AS REQUIRED. |
| | |
| | 3- ENGINEER OF RECORD TO PROVIDE COMPLETE SITE SPECIFIC |
| | DETAILS AND SPECIFICATIONS FOR THE ATTACHMENT OF THE |
| | SOLAR PANELS TO THE EXISTING ROOF. CLEARLY SPECIFY THE |
| | ANCHOR TYPES, SCREWS SIZES, ETC AND LOCATIONS SHOWING |
| | HOW THE OVERALL PANEL GRID IS GOING TO BE SECURED TO |
| | THE ROOF TO RESIST THE WIND LOADS. R301.2.1 |
| | FBC-RESIDENTIAL AND SEC. 107.2.1.2 CITY AMENDMENTS. |
| | NOTE: CLEARLY IDENTIFY WHERE ARE THE ANCHORS ATTACHED |
| | TO. FOR EXAMPLE ROOF TRUSSES. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. (NOTE: SUBMIT OLD DRAWINGS FOR REFERENCE). A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |