2020-07-13 16:33:24ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 210.52(E)(3) BALCONIES, DECKS, AND PORCHES. BALCONIES,
 DECKS, AND PORCHES THAT ARE ATTACHED TO THE DWELLING
 UNIT AND ARE ACCESSIBLE FROM INSIDE THE DWELLING UNIT
 SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE
 FROM THE BALCONY, DECK, OR PORCH. THE RECEPTACLE OUTLET
 SHALL NOT BE LOCATED MORE THAN 2.0 M (61/2 FT) ABOVE
 THE BALCONY, DECK, OR PORCH WALKING SURFACE