| Plan Review Notes For Permit 20050443 |
| Permit Number |
20050443 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2020-08-31 08:30:41 | DATE: MON. JULY 27TH/ AUGUST 31ST/ / 2020 | | | ACTION:BUILDING PROVISO | | | | | | 1) SHEET A1 INDICATES THE AIR HANDLER IS TO BE | | | REPLACED, NOTE 5 INDICATES DUCT WORK TO REMAIN. | | | IF THE BI-FOLD DOORS ARE USED TO TRANSFER THE RETURN | | | AIR TO THE UNIT THEN THE LOUVER DOORS NEED TO BE METAL. | | | 2017 FBC-B SECTION 2801.1 MECHANICAL EQUIPMENT AND | | | SYSTEMS SHALL BE CONSTRUCTED, INSTALLED AND MAINTAINED | | | IN ACCORDANCE WITH THE FBC-M AND FBC-B FOR PLENUMS. | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
|