2020-08-04 12:17:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20050442 3800 WASHINGTON RD 212
  
 2ND REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 1. SECOND REQUEST: FLORIDA ADMINISTRATIVE CODE
 61G15-23.005 (3)(C) A SCANNED, FACSIMILE, DIGITALLY
 CREATED OR COPIED IMAGE OF THE LICENSEE?S SIGNATURE
 SHALL NOT BE USED ON ELECTRONICALLY SIGNED AND SEALED
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
 PLEASE NOTE, THE SUBMITTED DOCUMENTS ARE SCANNED, THE
 SCANNED DIGITAL SIGNATURE CANNOT BE VERIFIED.
  
 2. NEW COMMENT: PLAN SHEET A.2; THE REFURBISHMENT OF
 THE EXISTING SHOWER DOES NOT INCLUDE REPLACEMENT OF THE
 SHOWER LINER. THE EXISTING LINER SHALL BE TESTED AND
 SHALL MEET ALL REQUIREMENTS OF FBC PL 417.5.2
 INCLUDING, BUT NOT LIMITED TO SLOPE TO THE DRAIN. IF
 DEEMED DEFICIENT BY THE PLUMBING INSPECTOR IT SHALL BE
 REPLACED. A DRAWING OF RECORD WILL BE REQUIRED
 INDICATING THE NEW LINER.
  
 3. NEW COMMENT: PLAN SHEET A.2; THE REFURBISHMENT OF
 THE EXISTING SHOWER DOES NOT INCLUDE REPLACEMENT OF THE
 CONTROL VALVE. THE EXISTING CONTROL VALVE SHALL BE
 TESTED AND SHALL MEET ALL REQUIREMENTS OF FBC PL 424.3
 INCLUDING, BUT NOT LIMITED TO BEING ANTI-SCALD. IF
 DEEMED DEFICIENT BY THE PLUMBING INSPECTOR IT SHALL BE
 REPLACED. A DRAWING OF RECORD WILL BE REQUIRED
 INDICATING THE CONTROL VALVE CONFORMING TO FBC PL
 424.3..
  
 4. NEW COMMENT: MASTER BATH TUB IS BEING REMOVED AND
 REPLACED WITH A SHOWER. THIS WILL REQUIRE MODIFICATION
 OF WATER PIPING AND IN WALL CONTROL VALVE. PER WPB FBC
 107.2.1, INDICATE ON THE PLANS AND SPECIFY THE CONTROL
 VALVE TO COMPLY WITH FBC PL 424.3; INDIVIDUAL SHOWER
 AND TUB-SHOWER COMBINATION VALVES SHALL BE
 BALANCED-PRESSURE, THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO
 THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA
 B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE
 INSTALLED AT THE POINT OF USE. SHOWER AND TUB-SHOWER
 COMBINATION VALVES REQUIRED BY THIS SECTION SHALL BE
 EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM SETTING OF
 THE VALVE TO 120?F (49?C), WHICH SHALL BE FIELD
 ADJUSTED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTRUCTIONS. IN-LINE THERMOSTATIC VALVES SHALL NOT BE
 UTILIZED FOR COMPLIANCE WITH THIS SECTION.
  
 5. NEW COMMENT: MASTER BATH TUB IS BEING REMOVED AND
 REPLACED WITH A SHOWER. THIS WILL REQUIRE MODIFICATION
 OF THE BELOW SLAB PIPING. PER WPB FBC 107.2.1, SUBMIT A
 SLAB REPAIR DETAIL FOR REVIEW SHOWING COMPLIANCE WITH
 THE REQUIREMENTS OF FBC CHAPTER 7. SHOW TYPE OF
 MATERIAL OF SHOWER DRAIN PIPE. PROVIDE ASSEMBLY HAVING
 A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR TO BE
 USED FOR DEALING WITH THE SHOWER FLOOR PENETRATION AND
 THE ELIMINATED TUB DRAIN OPENING AS REQUIRED BY FBC
 714.4.1 THROUGH 714.4.4.1.2.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20050442 3800 WASHINGTON RD 212
  