| 2020-08-04 12:17:17 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20050442 3800 WASHINGTON RD 212 |
| | |
| | 2ND REVIEW |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. SECOND REQUEST: FLORIDA ADMINISTRATIVE CODE |
| | 61G15-23.005 (3)(C) A SCANNED, FACSIMILE, DIGITALLY |
| | CREATED OR COPIED IMAGE OF THE LICENSEE?S SIGNATURE |
| | SHALL NOT BE USED ON ELECTRONICALLY SIGNED AND SEALED |
| | ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| | DOCUMENTS. |
| | PLEASE NOTE, THE SUBMITTED DOCUMENTS ARE SCANNED, THE |
| | SCANNED DIGITAL SIGNATURE CANNOT BE VERIFIED. |
| | |
| | 2. NEW COMMENT: PLAN SHEET A.2; THE REFURBISHMENT OF |
| | THE EXISTING SHOWER DOES NOT INCLUDE REPLACEMENT OF THE |
| | SHOWER LINER. THE EXISTING LINER SHALL BE TESTED AND |
| | SHALL MEET ALL REQUIREMENTS OF FBC PL 417.5.2 |
| | INCLUDING, BUT NOT LIMITED TO SLOPE TO THE DRAIN. IF |
| | DEEMED DEFICIENT BY THE PLUMBING INSPECTOR IT SHALL BE |
| | REPLACED. A DRAWING OF RECORD WILL BE REQUIRED |
| | INDICATING THE NEW LINER. |
| | |
| | 3. NEW COMMENT: PLAN SHEET A.2; THE REFURBISHMENT OF |
| | THE EXISTING SHOWER DOES NOT INCLUDE REPLACEMENT OF THE |
| | CONTROL VALVE. THE EXISTING CONTROL VALVE SHALL BE |
| | TESTED AND SHALL MEET ALL REQUIREMENTS OF FBC PL 424.3 |
| | INCLUDING, BUT NOT LIMITED TO BEING ANTI-SCALD. IF |
| | DEEMED DEFICIENT BY THE PLUMBING INSPECTOR IT SHALL BE |
| | REPLACED. A DRAWING OF RECORD WILL BE REQUIRED |
| | INDICATING THE CONTROL VALVE CONFORMING TO FBC PL |
| | 424.3.. |
| | |
| | 4. NEW COMMENT: MASTER BATH TUB IS BEING REMOVED AND |
| | REPLACED WITH A SHOWER. THIS WILL REQUIRE MODIFICATION |
| | OF WATER PIPING AND IN WALL CONTROL VALVE. PER WPB FBC |
| | 107.2.1, INDICATE ON THE PLANS AND SPECIFY THE CONTROL |
| | VALVE TO COMPLY WITH FBC PL 424.3; INDIVIDUAL SHOWER |
| | AND TUB-SHOWER COMBINATION VALVES SHALL BE |
| | BALANCED-PRESSURE, THERMOSTATIC OR COMBINATION |
| | BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO |
| | THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA |
| | B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE |
| | INSTALLED AT THE POINT OF USE. SHOWER AND TUB-SHOWER |
| | COMBINATION VALVES REQUIRED BY THIS SECTION SHALL BE |
| | EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM SETTING OF |
| | THE VALVE TO 120?F (49?C), WHICH SHALL BE FIELD |
| | ADJUSTED IN ACCORDANCE WITH THE MANUFACTURER?S |
| | INSTRUCTIONS. IN-LINE THERMOSTATIC VALVES SHALL NOT BE |
| | UTILIZED FOR COMPLIANCE WITH THIS SECTION. |
| | |
| | 5. NEW COMMENT: MASTER BATH TUB IS BEING REMOVED AND |
| | REPLACED WITH A SHOWER. THIS WILL REQUIRE MODIFICATION |
| | OF THE BELOW SLAB PIPING. PER WPB FBC 107.2.1, SUBMIT A |
| | SLAB REPAIR DETAIL FOR REVIEW SHOWING COMPLIANCE WITH |
| | THE REQUIREMENTS OF FBC CHAPTER 7. SHOW TYPE OF |
| | MATERIAL OF SHOWER DRAIN PIPE. PROVIDE ASSEMBLY HAVING |
| | A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR TO BE |
| | USED FOR DEALING WITH THE SHOWER FLOOR PENETRATION AND |
| | THE ELIMINATED TUB DRAIN OPENING AS REQUIRED BY FBC |
| | 714.4.1 THROUGH 714.4.4.1.2. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| | DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | |