| Date |
Text |
| 2020-05-31 15:37:24 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20050423 |
| | ADD: 630 S. SAPODILLA AVE. SUITE: 515 |
| | CONT: THE AREA GROUP |
| | TEL: 561-727-8904 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SUN. MAY 31ST/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) SUBMITTED THIS REVIEW WAS A MSDS SHEET FOR WHISPER |
| | MAT, NOTE IT WAS FOR WHISPER MAT CS, HW & HW/PLUS. |
| | PLEASE NOTE THE TYPE OF FLOOR FINISH AND UNDER LAYMENT |
| | NEEDS TO BE SPECIFIC TO THE PROJECT, |
| | |
| | FLOOR INSULATION (FBC-B 2017) |
| | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | |
| | TYPE I AND II BUILDINGS |
| | 1A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 1B) FBC-B 2017 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 1C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 2) CERTIFICATION BY CONTRACTOR. 107.3.4.3 CERTIFICATION |
| | BY CONTRACTOR. PLEASE NOTE THE EXCEPTION TO ENGINEERED |
| | PLANS UNDER 471.003(H) ELECTRICAL/ PLUMBING/ |
| | MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES THE |
| | CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN THAT |
| | TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS THE |
| | SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER) |
| | THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO |
| | IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE |
| | PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR |
| | THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN. FOR EACH |
| | TRADE THE CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER |
| | THE TRADE LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR |
| | NAME AND LICENSE NUMBER, NOTE THESE PLANS APPEAR TO BE |
| | DRAWN BY ONE INDUVIAL, THEY WOULD HAVE TO BE LICENSED |
| | AS A BUILDING, ELECTRICAL AND PLUMBING CONTRACTOR TO |
| | SUBMIT ALL THESE TRADES UNDER ONE SHEET. |
| | |
| | 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME IF YOU WOULD LIKE |
| | TO CONTACT ME, MY CELL NUMBER IS 561-718-9724. |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |