| 2020-08-06 07:35:04 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20050410 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE DATURA OCCUPANCY PERMIT APPLICATION SUBMITTED IS |
| | REQUESTING A HIGHER OCCUPANCY GOING FROM 93 TO 166 |
| | OCCUPANTS. THE SUBMITTED MECHANICAL DOCUMENTS ? DATURA |
| | BAR UPDATED LOADS PER NEW OCCUPANCY? INDICATES THAT |
| | RTTU-1 IS SIZED FOR 26 OCCUPANTS; RTU-2 IS SIZED FOR 58 |
| | OCCUPANTS; AND RTU-3 IS SIZED FOR 61 OCCUPANTS. |
| | THEREFORE THE OCCUPANT LOAD FOR THESE SYSTEMS COMBINED |
| | IS FOR 145 OCCUPANTS. BASED ON THE SUBMITTED MECHANICAL |
| | SYSTEM CALCULATIONS THIS PROJECT WILL ONLY SUPPORT A |
| | TOTAL OF 145 OCCUPANTS NOT 166 OCCUPANTS. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |