| Date |
Text |
| 2020-05-27 08:00:36 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20050410 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED.- |
| | |
| | 1) PLEASE PROVIDE MORE INFORMATION ABOUT PROJECT. IS |
| | THE RESTAURANT TAKING OVER THE BUSINESS AREA OF THIS |
| | BUILDING? HOW WILL THE PATRONS ACCESS THIS AREA, I DO |
| | NOT SEE A DOOR GOING FROM RESTAURANT TO NEW AREA. FBC |
| | FS 107.2.1 |
| | |
| | 2) PROVIDE VENTILATION CALCULATIONS FOR THIS CHANGE OF |
| | USE AND CHANGE OF OCCUPANCY. FBC M TABLE 403.3.1.1 |
| | |
| | 3) PLEASE SHOW HOW THE EXISTING UNIT WILL PROVIDE |
| | VENTILATION AND IS SIZED CORRECTLY FOR THE ADDITIONAL |
| | OCCUPANT COUNT. (GOING FROM BUSINESS TO A-2) FBC FS |
| | 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |