Plan Review Notes
Plan Review Notes For Permit 20050379
Permit Number 20050379
Review Stop M
Sequence Number 2
Notes
Date Text
2020-10-15 07:17:071ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20050379
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IT APPEARS THAT AHU #2 IS LOCATED IN A CLOSET INSIDE
 THE LAUNDRY ROOM. THE LAUNDRY HAS A DOOR CLOSING IT OFF
 FROM THE HALL. THE RETURN AIR FROM THE BEDROOMS IS
 BEING DUCTED BACK INTO THE HALL. PLEASE SHOW THAT WHEN
 THE LAUNDRY ROOM DOOR IS SHUT THAT THIS INSTILLATION
 MEETS FBC RES M1602.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  