Plan Review Notes
Plan Review Notes For Permit 20050379
Permit Number 20050379
Review Stop P
Sequence Number 1
Notes
Date Text
2020-11-02 13:49:3111/02/20 1 ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PAGE 1.0 AND PAGE 1.1 HAVE MOST OF THE SAME
 INFORMATION DUPLICATED. PAGE 1.1 IS MISSING THE
 PREVIUOS PLUMBING INFORMATION OF THE PAGE SUBMITTED ON
 05/15/20 FOR ISOMETRIC AND SHOWER DETAIL WHICH IS
 REQUIRED PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.3.5.3 (11) RESIDENTIAL PLUMBING
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  