Plan Review Notes
Plan Review Notes For Permit 20050372
Permit Number 20050372
Review Stop B
Sequence Number 1
Notes
Date Text
2020-05-21 08:20:582017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20050372
 ADD: 1200 S FLAGLER DR. SUITE: PH-03
 CONT: DMF CONSTRUCTION INC.
 TEL: 561-768-8988
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. MAY 21/2020
 ACTION: DENIED
  
 1) THE VALUE OF THIS PERMIT SEEMS LOW FOR THE
 DESCRIPTION OF WORK, PLANS TO BE DEVELOPED, COST
 INCURRED FOR THE S.I, B.N., MATERIALS AND LABOR,
 REMOVAL OF DEBRIS, PROFIT AND OVERHEAD.
 109.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 2) THE SCOPE OF WORK CONCRETE RESTORATION &
 REHABILITATION IS GOING TO TAKE PLACE ON A THRESHOLD
 BUILDING. DOCUMENTS SUBMITTED INCLUDE A THRESHOLD
 AGREEMENT. THIS AGREEMENT HAS THE SIGNATURES OF THE
 S.I., JOBSITE BN, AND OWNER. THE THRESHOLD AGREEMENT IS
 MISSING THE CONTRACTORS SIGNATURE, THIS SIGNATURE IS
 REQUIRED TO COMPLETE ALL PARTIES CONCERNED TO COMPLETE
 THIS DOCUMENT.
  
 3) UNDER THE SCOPE OF WORK CONCRETE RESTORATION &
 REHABILITATION NO PLANS WERE SUBMITTED. THE SUBMITTED
 DOCUMENTS STATE THE S. I. WILL GO TO THE JOBSITE TO
 INVESTIGATE HOW FAR THE STUCCO AND CONCRETE WORK WILL
 NEED TO BE REMOVED TO OBTAIN STRUCTURAL SOUND REBAR?S
 FOR BOTH SLAB AND COLUMNS. THERE IS NO MENTION OF, IF
 REQUIRED SHORING AND RESHORING WOULD BE REQUIRED AND
 DETAILS TO FOLLOW. 107.2.1.2.
  
 4) IN THE SCOPE OF WORK THE DOCUMENT DOES STATE THAT
 THE WINDOW WALL SYSTEMS WILL BE REMOVED TO MAKE
 STRUCTURAL REPAIRS TO THE CONCRETE SLAB. IN SPEAKING
 WITH CHIEF BUILDING INSPECTOR KEN CONRAD HE WAS IN THE
 BELIEF THAT NEW WINDOW/ SLIDING GLASS DOOR SYSTEMS WILL
 BE INSTALLED. IS THIS WORK TO OCCUR UNDER THIS PERMIT
 OR UNDER A SEPARATE PERMIT. NO DOCUMENTS WERE
 SUBMITTED.
  
 4A) WIND DESIGN CRITERIA.
  
 4B) PRODUCT APPROVALS FOR SLIDING GLASS DOORS AND OR
 WINDOWS.
  
 4C) IDENTIFICATION OF GLAZING TYPES, MULLIONS, SILL
 HEIGHTS, PRESSURES AND ANCHORAGE.
  
 4D) DESIGNERS SHOP DRAWING STAMP OF APPROVAL.
  
 5) IN THE SUBMITTED DOCUMENTS THE ACRI SPECIFICATIONS
 FOR CONCRETE BUILDINGS IS REFERENCED PLEASE SUBMIT
 DETAILS FOR REVIEW.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME IF YOU WOULD LIKE
 TO CONTACT ME, MY CELL NUMBER IS 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  