| 2020-09-02 13:39:40 | 09/02/20 2 ND GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLEASE NOTE THAT IF A GAS REVIEW IS DONE IT MUST BE |
| | COMPLETED AND A SEPARATE GAS SUB PERMIT WILL BE ISSUED |
| | BUT ALL COMMENTS AND CONCERNS HAVE TO BE ADDRESSED BY |
| | REGISTERED ARCHITECT. |
| | |
| | 2. SIGNED AND SEALED DRAWINGS NEED TO BE |
| | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR - |
| | IF YOUR ENGINEER DOES NOT HAVE A ELECTRONIC OR DIGITAL |
| | SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE |
| | ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN |
| | REVIEW REQUEST FORM" EXPLAINING THE REASON FOR |
| | SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW |
| | REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected] |
| | AND ASKING FOR THE FORM. |
| | |
| | 3. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. ON PLANS IT SAYS FIRE PLACE, FIRE BAR AND FIRE PIT, |
| | THERE IS ONLY ONE SPECIFICATION SUBMITTED AND IS IT A |
| | FIRE PLACE, ARE THE TWO FIRE PLACES IN THE HOUSE THE |
| | SAME AND IF NOT PLEASE SUBMIT OR RELABEL ON ISOMETRIC |
| | FOR CLARITY ON PLANS PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 5. SHEET A-1 SHOW ELECTRIC WATER HEATER, PLEASE REMOVE |
| | AND SHOW GAS TYPE PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 6. SHEET 023 P-5 IS LABELED AS ISOMETRIC GAS RISER |
| | WHICH HAS NO DETAIL ABOUT GAS AND 035 P-8 HAS THE |
| | ISOMETRIC INFORMATION PLEASE SWAP AND SHOW. P-5 HAS A |
| | STORAGE TANK WATER HEATER PLEASE CHANGE AND DELETE |
| | INFORMATION NOT PERTAINING TO PLANS PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 7. THE TANK-LEES HEATER SPECIFICATION HAS 160 BTU'S BUT |
| | THE ISOMETRIC HAS 300 BTU'S PLEASE RECALCULATE AND |
| | DOUBLE CHECK ALL BTU'S TO COORDINATE WITH ISOMETRIC |
| | TOTAL BTU'S PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 8. THE TANK-LESS GAS HEATER HAS A CONDENSATE LINE THAT |
| | DRIP CONSTANTLY PLEASE MAKE A NOTE THAT THAT SHALL BE |
| | 1' AWAY FROM BUILDING PER THE 2017 FBC SEC G318.5. |
| | |
| | 9. PLEASE LIST THE BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2017 |
| | FBC-RES. SEC. G2413.3, G2413.4 AND TABLES G2413.4 (1 ) |
| | THROUGH G2413.4 (21). CONTRACTOR TO STATE WHICH TABLES |
| | ARE USED. |
| | |
| | 10. THESE TANK-LESS UNIT CALL FOR 10.5" WATER COLUMN |
| | WHICH REQUIRING A REGULATOR FOR THIS UNIT AS PER |
| | MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES. |
| | SEC. G2421.1. |
| | |
| | 11. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1' OF |
| | EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2. |
| | |
| | 12. SHOW DRIP LEG ON EQUIPMENT INSTALLED EXCEPT FOR |
| | APPLIANCES, RANGE, DRYERS & OD GRILLS PER THE 2017 FBC |
| | RES. SEC. G2419.2. |
| | |
| | 13. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| | FBC FG SEC. 304.1, 614.5 (CLOTHES DRYERS COOK TOP AND |
| | OVEN) OR 2017 FBC RES. SEC. G2407.1 AND G2439.4. |
| | |
| | 14. IF USING LOVERS, PLEASE SHOW THE LOCATION OF THE |
| | METAL OR WOOD LOUVERS THAT ARE BEING INSTALLED FOR THE |
| | COMBUSTION AIR. THE LOUVERS CANNOT BE LOCATED ON AN |
| | EXTERIOR WALL THAT IS FIRE RATED AS THE FIRE RATING OF |
| | THE WALL MUST BE MAINTAINED PER THE WPB AMENDMENTS TO |
| | FBC SEC.107.2.1. |
| | |
| | 15. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER 2017 FBC RES. SEC. G2413.2. |
| | |
| | 16. SUBMIT MANUFACTURER?S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT (FIRE |
| | PIT, FIRE BAR/OUTDOOR GRILL, COOK TOP AND DRYER) TO |
| | VERIFY COMPLIANCE, WITH STANDARDS NFPA 54, NFPA 58, AND |
| | 2017 FBC-RES. SEC. G2404.3. |
| | |
| | 17. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION. FBC-RES. |
| | SEC. G2408.1. |
| | |
| | 18. THE ISOMETRIC SHOWS A GAS GRILL PLEASE INDICATE ON |
| | THE PLAN IF THE GRILL IS LOCATED UNDER A ROOF AND IF IN |
| | A COVERED PATIO, PLEASE PROVIDE MANUFACTURES |
| | RECOMMENDATION FOR A VENTILATION HOOD PER THE 2017 FBC |
| | RES. SEC. G2408.1. |
| | |
| | 19. SUBMIT ON A HOUSE PLAN SHOWING THE LOCATION OF THE |
| | TANK-LESS WATER HEATER AND THE LOCATION AND DISTANCE OF |
| | ANY OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER |
| | HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY |
| | WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 20. THESE IS A FIRE PIT SHOW ON ISOMETRIC BUT NOT ON |
| | FLAT PLAN PLEASE SHOW LOCATION PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |
| | |