2020-09-02 13:39:4009/02/20 2 ND GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE NOTE THAT IF A GAS REVIEW IS DONE IT MUST BE
 COMPLETED AND A SEPARATE GAS SUB PERMIT WILL BE ISSUED
 BUT ALL COMMENTS AND CONCERNS HAVE TO BE ADDRESSED BY
 REGISTERED ARCHITECT.
  
 2. SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE A ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM.
  
 3. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. ON PLANS IT SAYS FIRE PLACE, FIRE BAR AND FIRE PIT,
 THERE IS ONLY ONE SPECIFICATION SUBMITTED AND IS IT A
 FIRE PLACE, ARE THE TWO FIRE PLACES IN THE HOUSE THE
 SAME AND IF NOT PLEASE SUBMIT OR RELABEL ON ISOMETRIC
 FOR CLARITY ON PLANS PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. SHEET A-1 SHOW ELECTRIC WATER HEATER, PLEASE REMOVE
 AND SHOW GAS TYPE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 6. SHEET 023 P-5 IS LABELED AS ISOMETRIC GAS RISER
 WHICH HAS NO DETAIL ABOUT GAS AND 035 P-8 HAS THE
 ISOMETRIC INFORMATION PLEASE SWAP AND SHOW. P-5 HAS A
 STORAGE TANK WATER HEATER PLEASE CHANGE AND DELETE
 INFORMATION NOT PERTAINING TO PLANS PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 7. THE TANK-LEES HEATER SPECIFICATION HAS 160 BTU'S BUT
 THE ISOMETRIC HAS 300 BTU'S PLEASE RECALCULATE AND
 DOUBLE CHECK ALL BTU'S TO COORDINATE WITH ISOMETRIC
 TOTAL BTU'S PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 8. THE TANK-LESS GAS HEATER HAS A CONDENSATE LINE THAT
 DRIP CONSTANTLY PLEASE MAKE A NOTE THAT THAT SHALL BE
 1' AWAY FROM BUILDING PER THE 2017 FBC SEC G318.5.
  
 9. PLEASE LIST THE BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2017
 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES G2413.4 (1 )
 THROUGH G2413.4 (21). CONTRACTOR TO STATE WHICH TABLES
 ARE USED.
  
 10. THESE TANK-LESS UNIT CALL FOR 10.5" WATER COLUMN
 WHICH REQUIRING A REGULATOR FOR THIS UNIT AS PER
 MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES.
 SEC. G2421.1.
  
 11. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1' OF
 EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2.
  
 12. SHOW DRIP LEG ON EQUIPMENT INSTALLED EXCEPT FOR
 APPLIANCES, RANGE, DRYERS & OD GRILLS PER THE 2017 FBC
 RES. SEC. G2419.2.
  
 13. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC FG SEC. 304.1, 614.5 (CLOTHES DRYERS COOK TOP AND
 OVEN) OR 2017 FBC RES. SEC. G2407.1 AND G2439.4.
  
 14. IF USING LOVERS, PLEASE SHOW THE LOCATION OF THE
 METAL OR WOOD LOUVERS THAT ARE BEING INSTALLED FOR THE
 COMBUSTION AIR. THE LOUVERS CANNOT BE LOCATED ON AN
 EXTERIOR WALL THAT IS FIRE RATED AS THE FIRE RATING OF
 THE WALL MUST BE MAINTAINED PER THE WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 15. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC RES. SEC. G2413.2.
  
 16. SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT (FIRE
 PIT, FIRE BAR/OUTDOOR GRILL, COOK TOP AND DRYER) TO
 VERIFY COMPLIANCE, WITH STANDARDS NFPA 54, NFPA 58, AND
 2017 FBC-RES. SEC. G2404.3.
  
 17. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FBC-RES.
 SEC. G2408.1.
  
 18. THE ISOMETRIC SHOWS A GAS GRILL PLEASE INDICATE ON
 THE PLAN IF THE GRILL IS LOCATED UNDER A ROOF AND IF IN
 A COVERED PATIO, PLEASE PROVIDE MANUFACTURES
 RECOMMENDATION FOR A VENTILATION HOOD PER THE 2017 FBC
 RES. SEC. G2408.1.
  
 19. SUBMIT ON A HOUSE PLAN SHOWING THE LOCATION OF THE
 TANK-LESS WATER HEATER AND THE LOCATION AND DISTANCE OF
 ANY OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER
 HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 20. THESE IS A FIRE PIT SHOW ON ISOMETRIC BUT NOT ON
 FLAT PLAN PLEASE SHOW LOCATION PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR