Plan Review Notes
Plan Review Notes For Permit 20050315
Permit Number 20050315
Review Stop B
Sequence Number 2
Notes
Date Text
2020-09-14 14:29:41NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 2ND REVIEW
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 1) PLEASE PROVIDE DETAILS FOR THE METAL FRAMING FRONT
 CANOPY AND BOX OUTS - SHOW ALL FRAMING DESIGNATIONS AND
 ATTACHMENTS TO COMPLY WITH THE DESIGN WIND LOADS PER
 DRAWING S.9 ( PLEASE SHOW ATTACHMENT OF THE FRAMING TO
 THE CONCRETE STRUCTURE)
  
 2) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT
 APPROVAL REQUIRES ADDITIONAL SIGNED AND SEALED
 ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR
 ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER PRESSURE
 THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL (-52.5)
 - SEE GENERAL LIMITATION NOTE NUMBER 7 ON THE PRODUCT
 APPROVAL.)
  
 3) PLEASE PROVIDE A DIGITALLY SIGNED AND SEALED SURVEY
 SHOWING THE FLOOD ZONE PER THE LATEST FIRM . FBC WPB
 AMENDMENTS 107.2.5
  
 4) GARAGE FINISHED FLOOR ELEVATIONS BELOW FEMA BASE
 FLOOD ELEVATION ARE REQUIRED TO HAVE FLOOD VENTS PER
 FBC R322.2.2 PLEASE PROVIDE THE REQUIRED STATEMENT - (A
 STATEMENT BY A REGISTERED DESIGN PROFESSIONAL THAT THE
 DESIGN OF THE OPENINGS WILL PROVIDE FOR EQUALIZATION OF
 HYDROSTATIC FLOOD FORCES ON EXTERIOR WALLS BY ALLOWING
 FOR THE AUTOMATIC ENTRY AND EXIT OF FLOODWATERS AS
 SPECIFIED IN SECTION 2.7.2.2 OF ASCE 24.)
 R322.2.2 ENCLOSED AREA BELOW DESIGN FLOOD ELEVATION.
 (2.) BE PROVIDED WITH FLOOD OPENINGS THAT MEET THE
 FOLLOWING CRITERIA AND ARE INSTALLED IN ACCORDANCE WITH
 SECTION R322.2.2.1:
  
 2.1.THE TOTAL NET AREA OF NON-ENGINEERED OPENINGS SHALL
 BE NOT LESS THAN 1 SQUARE INCH (645 MM2) FOR EACH
 SQUARE FOOT (0.093 M2) OF ENCLOSED AREA WHERE THE
 ENCLOSED AREA IS MEASURED ON THE EXTERIOR OF THE
 ENCLOSURE WALLS, OR THE OPENINGS SHALL BE DESIGNED AS
 ENGINEERED OPENINGS AND THE CONSTRUCTION DOCUMENTS
 SHALL INCLUDE A STATEMENT BY A REGISTERED DESIGN
 PROFESSIONAL THAT THE DESIGN OF THE OPENINGS WILL
 PROVIDE FOR EQUALIZATION OF HYDROSTATIC FLOOD FORCES ON
 EXTERIOR WALLS BY ALLOWING FOR THE AUTOMATIC ENTRY AND
 EXIT OF FLOODWATERS AS SPECIFIED IN SECTION 2.7.2.2 OF
 ASCE 24.
  
 2.2.OPENINGS SHALL BE NOT LESS THAN 3 INCHES (76 MM) IN
 ANY DIRECTION IN THE PLANE OF THE WALL.
  
 2.3.THE PRESENCE OF LOUVERS, BLADES, SCREENS AND
 FACEPLATES OR OTHER COVERS AND DEVICES SHALL ALLOW THE
 AUTOMATIC FLOW OF FLOODWATER INTO AND OUT OF THE
 ENCLOSED AREAS AND SHALL BE ACCOUNTED FOR IN THE
 DETERMINATION OF THE NET OPEN AREA.
  
 5) EQUIPMENT SHOWN IN THE GARAGE AND OUTSIDE THE
 BUILDING (WASHER, DRYER, AC ETC.) WILL NEED TO BE
 ELEVATED TO COMPLY WITH FBC R322.1.6
  
 6) PLEASE SHOW THE REQUIRED RAILING AT THE 2ND FLOOR
 "OPENING TO BELOW". FBC R312
  
 7) PLEASE PROVIDE A COMPLETED ELEVATION CERTIFICATE -
 MARKED ( CONSTRUCTION DRAWINGS). FBC WPB AMENDMENTS
 107.3.5.1.1 (1)
  
  
  