2020-06-08 15:29:58PLAN REVIEW - PLUMBING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SHOWER PAN DETAIL.
 P2709.1 SHOWER PAN CONSTRUCTION. FBC 107.2.1
  
 2. LABEL ALL PIPE SIZES ON SANITARY RISER.
 P3005.4DRAIN PIPE SIZING.
  
 3. PROVIDE WATER DISTRIBUTION RISER DIAGRAHM.
 P2903.1WATER SUPPLY SYSTEM DESIGN CRITERIA.THE WATER
 SERVICE AND WATER DISTRIBUTION SYSTEMS SHALL BE
 DESIGNED, AND PIPE SIZES SHALL BE SELECTED SUCH THAT
 UNDER CONDITIONS OF PEAK DEMAND, THE CAPACITIES AT THE
 POINT OF OUTLET DISCHARGE SHALL NOT BE LESS THAN SHOWN
 IN TABLE P2903.1.
  
 4. PROVIDE THERMOSTATIC SHOWER CONTROL VALVES.
 P2708.4SHOWER CONTROL VALVES. INDIVIDUAL SHOWER AND
 TUB/ SHOWER COMBINATION VALVES SHALL BE EQUIPPED WITH
 CONTROL VALVES OF THE PRESSURE-BALANCE,
 THERMOSTATIC-MIXING OR COMBINATION
 PRESSURE-BALANCE/THERMOSTATIC-MIXING VALVE TYPES WITH A
 HIGH LIMIT STOP IN ACCORDANCE WITH ASSE 1016/ASME
 A112.1016/CSA B125.16. THE HIGH LIMIT STOP SHALL BE SET
 TO LIMIT THE WATER TEMPERATURE TO NOT GREATER THAN
 120?F (49?C). IN-LINE THERMOSTATIC VALVES SHALL NOT BE
 USED FOR COMPLIANCE WITH THIS SECTION.
  
  
  
  
  
  