2020-06-08 15:31:05PLAN REVIEW ? FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE
 PER 2017 FBC-R SEC. G2413.4.1, G2413.4.2.
  
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING
  
 (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 3. TYPE OF GAS (LP OR NATURAL).WPB AMEND. TO FBC SEC.
 107.2.1.
  
 4. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-RES. SEC.
 G2413.3, G2413.4 AND TABLES G2413.4 (1 ) THROUGH
 G2413.4 (21). CONTRACTOR TO STATE WHICH TABLES ARE
 USED.
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-RES. SEC. G 2413.4.1, G2413.4.2.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES DRYERS).
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC RES. SEC. G2413.2, G2413.4.3.
  
 8. SUBMIT TWO COPIES OF A DETAIL SHOWING THE TYPE OF
 VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE
 THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER
 2017 FBC-RES. SEC.G2426 THROUGH G2439.
  
 9. SUBMIT TWO COPIES OF THE MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FBC-RES. SEC.G2408.1.
  
  