Plan Review Notes
Plan Review Notes For Permit 20050315
Permit Number 20050315
Review Stop E
Sequence Number 1
Notes
Date Text
2020-06-04 09:54:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-1 AND E-2
  
 1) PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC R315.1 NOT
 ALL LOCATED WITHIN 10' OF THE SLEEPING AREAS.
  
 PAGE E=3
  
 2) PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT
 CURRENT AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE.
 NEC 110.10
  
 3) PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE3602.3
  
 4) GROUND ROD AT PANELS ???
  
 5) PANEL SCHEDULE SHALL BE LEGIBLY IDENTIFIED AS TO
 THEIR CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. THE
 IDENTIFICATION SHALL INCLUDE SUFFICIENT DETAIL TO ALLOW
 EACH CIRCUIT TO BE DISTINGUISHED FROM ALL OTHERS. SPARE
 POSITIONS THAT CONTAIN UNUSED OVERCURRENT DEVICES OR
 SWITCHES SHALL BE DESCRIBED ACCORDINGLY. THE
 IDENTIFICATION SHALL BE INCLUDED IN A CIRCUIT DIRECTORY
 LOCATED ON THE FACE OF THE PANELBOARD ENCLOSURE OR
 INSIDE THE PANEL DOOR. CIRCUITS SHALL NOT BE DESCRIBED
 IN A MANNER THAT DEPENDS ON TRANSIENT CONDITIONS OF
 OCCUPANCY. FBC RE3706. OUTLETS AND LIGHTS NOT
 ACCEPTABLE.
  
 6) NOTE #5 CALLS FOR EMT UNDERGROUND, EMT NOT ALLOWED
 IN THE EARTH WITHOUT A CORROSION INHIBITOR. 358.10(B)
 CORROSION PROTECTION. FERROUS OR NONFERROUS EMT,
 ELBOWS, COUPLINGS, AND FITTINGS SHALL BE PERMIT TED TO
 BE INSTALLED IN CONCRETE, IN DIRECT CONTACT WITH THE
 EARTH, OR IN AREAS SUBJECT TO SEVERE CORROSIVE
 INFLUENCES WHERE PROTECTED BY CORROSION PROTECTION AND
 APPROVED AS SUITABLE FOR THE CONDITION.
  
 PAGE E-1
  
 7) PROVIDE AN OUTLET (GFCI) WITH 6' AND NOT MORE THAN
 20' FROM POOL. E4203.1.2 WHERE REQUIRED. AT LEAST ONE
 125-VOLT, 15- OR 20-AMPERE RECEPTACLE SUPPLIED BY A
 GENERAL-PURPOSE BRANCH CIRCUIT SHALL BE LOCATED A
 MINIMUM OF 6 FEET (1829 MM) FROM AND NOT MORE THAN 20
 FEET (6096 MM) FROM THE INSIDE WALL OF POOLS AND
 OUTDOOR SPAS AND HOT TUBS. THIS RECEPTACLE SHALL BE
 LOCATED NOT MORE THAN 6 FEET, 6 INCHES (1981 MM) ABOVE
 THE FLOOR, PLATFORM OR GRADE LEVEL SERVING THE POOL,
 SPA OR HOT TUB. [680.22(A)(1)]