| 2020-06-04 09:54:21 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | PAGE E-1 AND E-2 |
| | |
| | 1) PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF |
| | EACH ROOM USED FOR SLEEPING PURPOSES. FBC R315.1 NOT |
| | ALL LOCATED WITHIN 10' OF THE SLEEPING AREAS. |
| | |
| | PAGE E=3 |
| | |
| | 2) PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT |
| | CURRENT AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. |
| | NEC 110.10 |
| | |
| | 3) PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. NEC 220; FBC RE3602.3 |
| | |
| | 4) GROUND ROD AT PANELS ??? |
| | |
| | 5) PANEL SCHEDULE SHALL BE LEGIBLY IDENTIFIED AS TO |
| | THEIR CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. THE |
| | IDENTIFICATION SHALL INCLUDE SUFFICIENT DETAIL TO ALLOW |
| | EACH CIRCUIT TO BE DISTINGUISHED FROM ALL OTHERS. SPARE |
| | POSITIONS THAT CONTAIN UNUSED OVERCURRENT DEVICES OR |
| | SWITCHES SHALL BE DESCRIBED ACCORDINGLY. THE |
| | IDENTIFICATION SHALL BE INCLUDED IN A CIRCUIT DIRECTORY |
| | LOCATED ON THE FACE OF THE PANELBOARD ENCLOSURE OR |
| | INSIDE THE PANEL DOOR. CIRCUITS SHALL NOT BE DESCRIBED |
| | IN A MANNER THAT DEPENDS ON TRANSIENT CONDITIONS OF |
| | OCCUPANCY. FBC RE3706. OUTLETS AND LIGHTS NOT |
| | ACCEPTABLE. |
| | |
| | 6) NOTE #5 CALLS FOR EMT UNDERGROUND, EMT NOT ALLOWED |
| | IN THE EARTH WITHOUT A CORROSION INHIBITOR. 358.10(B) |
| | CORROSION PROTECTION. FERROUS OR NONFERROUS EMT, |
| | ELBOWS, COUPLINGS, AND FITTINGS SHALL BE PERMIT TED TO |
| | BE INSTALLED IN CONCRETE, IN DIRECT CONTACT WITH THE |
| | EARTH, OR IN AREAS SUBJECT TO SEVERE CORROSIVE |
| | INFLUENCES WHERE PROTECTED BY CORROSION PROTECTION AND |
| | APPROVED AS SUITABLE FOR THE CONDITION. |
| | |
| | PAGE E-1 |
| | |
| | 7) PROVIDE AN OUTLET (GFCI) WITH 6' AND NOT MORE THAN |
| | 20' FROM POOL. E4203.1.2 WHERE REQUIRED. AT LEAST ONE |
| | 125-VOLT, 15- OR 20-AMPERE RECEPTACLE SUPPLIED BY A |
| | GENERAL-PURPOSE BRANCH CIRCUIT SHALL BE LOCATED A |
| | MINIMUM OF 6 FEET (1829 MM) FROM AND NOT MORE THAN 20 |
| | FEET (6096 MM) FROM THE INSIDE WALL OF POOLS AND |
| | OUTDOOR SPAS AND HOT TUBS. THIS RECEPTACLE SHALL BE |
| | LOCATED NOT MORE THAN 6 FEET, 6 INCHES (1981 MM) ABOVE |
| | THE FLOOR, PLATFORM OR GRADE LEVEL SERVING THE POOL, |
| | SPA OR HOT TUB. [680.22(A)(1)] |