| 2020-06-02 15:50:50 | NEW SFR |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) PLEASE SHOW THE REQUIRED DRAFT STOPPING FOR THE |
| | CEILING / FLOOR ASSEMBLY TO COMPLY WITH FBC R302.12 |
| | 2) PLEASE SHOW THE REQUIRED HANDRAILS FOR ALL STAIRS |
| | (GARAGE TO LIVING SPACE) (FRONT ENTRY) TO COMPLY WITH |
| | FBC R311.7.8 (R311.3.1) |
| | 3) PLEASE SHOW THE WIDTH OF THE STAIRS IN GARAGE NUMBER |
| | 1 TO COMPLY WITH FBC R311.7.1 |
| | 4) BEDROOM NUMBER 3 DOES NOT COMPLY WITH EMERGENCY |
| | EGRESS REQUIREMENTS PER FBC R310.2.1 |
| | 5) PLEASE SHOW THE REQUIRED LENGTH OF THE LEDGER ANCHOR |
| | BOLTS FOR NOTE NUMBER 8 ON DRAWING (S.5) |
| | 6) DRAWING S.9 SHOWS WIND DESIGN PER ASCE 7-16 = SHOULD |
| | BE ASCE 7-10 PER FBC CHAPTER 35. |
| | 7) PLEASE PROVIDE DETAILS FOR THE METAL FRAMING FRONT |
| | CANOPY AND BOX OUTS - SHOW ALL FRAMING DESIGNATIONS AND |
| | ATTACHMENTS TO COMPLY WITH THE DESIGN WIND LOADS PER |
| | DRAWING S.9 |
| | 8) PLEASE PROVIDE COMPLETE PRODUCT APPROVALS FOR THE |
| | OVERHEAD GARAGE DOOR AND (SS-3500 IMPACT - RESISTANT |
| | STOREFRONT WINDOW SYSTEM) - NEED FRONT PAGES FOR THE |
| | MIAMI DADE OR FLORIDA STATE PRODUCT APPROVALS - ONLY |
| | THE INSTALLATION INSTRUCTIONS WERE PROVIDED. |
| | 9) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED |
| | APPROVED BY THE BUILDING DESIGNER OF RECORD. |
| | 10) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE ROOFING SYSTEM TO BE USED. |
| | 11) PRIVACY WALL SHALL BE ON A SEPARATE PERMIT - PLEASE |
| | MAKE NOTE ON THE DRAWING. |
| | 12) PLEASE PROVIDE A DIGITALLY SIGNED AND SEALED SURVEY |
| | SHOWING THE FLOOD ZONE PER THE LATEST FIRM AND THE |
| | PROPERTY DRAINAGE. |
| | 13) PALM BEACH COUNTY FLOOD MAPS SHOW THIS PROPERTY IN |
| | A FLOOD ZONE (AE 7) - PLEASE SHOW THE FINISHED FLOOR |
| | ELEVATION 2 FEET ABOVE THE BASE FLOOD ELEVATION (FFE = |
| | 9.00 NAVD) OR HIGHER. FBC R322.2.1 |
| | 14) GARAGE FINISHED FLOOR ELEVATIONS BELOW FEMA BASE |
| | FLOOD ELEVATION ARE REQUIRED TO HAVE FLOOD VENTS PER |
| | FBC R322.2.2 |
| | 15) EQUIPMENT SHOWN IN THE GARAGE AND OUTSIDE THE |
| | BUILDING (WASHER, DRYER, AC ETC.) WILL NEED TO BE |
| | ELEVATED TO COMPLY WITH FBC R322.1.6 |
| | 16) DRAWINGS SHOW "ICYNENE" INSULATION TO THE BOTTOM OF |
| | THE ROOF DECK AND VENTED ATTIC SPACE. SHOULD THE ATTIC |
| | BE VENTED? |
| | |
| | |