Plan Review Notes
Plan Review Notes For Permit 20050295
Permit Number 20050295
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-05-14 15:38:23THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE INDICATIONS OF PULL STATIONS THROUGHTOUT
 ALL FLOORS AT EXIT LOCATIONS.
  
 PER NFPA 101, CH 12
  
 12.3.4.2 INITIATION.
 12.3.4.2.1 INITIATION OF THE REQUIRED FIRE ALARM SYSTEM
 SHALL BE BY
 BOTH OF THE FOLLOWING MEANS:
 (1) MANUAL MEANS IN ACCORDANCE WITH 9.6.2.1(1), UNLESS
 OTHERWISE
 PERMITTED BY ONE OF THE FOLLOWING:
 (A) THE REQUIREMENT OF 12.3.4.2.1(1) SHALL NOT APPLY
 WHERE
 INITIATION IS BY MEANS OF AN APPROVED AUTOMATIC FIRE
 DETECTION SYSTEM IN ACCORDANCE WITH 9.6.2.1(2) THAT
 PROVIDES FIRE DETECTION THROUGHOUT THE BUILDING
 (B) THE REQUIREMENT OF 12.3.4.2.1(1) SHALL NOT APPLY
 WHERE
 INITIATION IS BY MEANS OF AN APPROVED AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH 9.6.2.1(3) THAT
 PROVIDES FIRE DETECTION AND PROTECTION THROUGHOUT THE
 BUILDING.
 (2) WHERE AUTOMATIC SPRINKLERS ARE PROVIDED, INITIATION
 OF THE
 FIRE ALARM SYSTEM BY SPRINKLER SYSTEM WATERFLOW, EVEN
 WHERE
 MANUAL FIRE ALARM BOXES ARE PROVIDED IN ACCORDANCE WITH
 12.3.4.2.1(1)
  
 PER NFPA 101, CH 9
  
 9.6.2.6* FOR FIRE ALARM SYSTEMS USING AUTOMATIC FIRE
 DETECTION OR
 WATERFLOW DETECTION DEVICES TO INITIATE THE FIRE ALARM
 SYSTEM IN
 ACCORDANCE WITH CHAPTERS 11 THROUGH 43, NOT LESS THAN
 ONE MANUAL
 FIRE ALARM BOX, LOCATED AS REQUIRED BY THE AUTHORITY
 HAVING
 JURISDICTION, SHALL BE PROVIDED TO INITIATE A FIRE
 ALARM SIGNAL.
  
 IN AN EFFORT TO REDUCE FALSE/ACCIDENTA/MALICIOUS ALARMS
 ALL BUT THREE (3) PULL STATIONS CAN BE REMOVED PER THE
 ABOVE NOTED CODE REFERENCES.
  
 ONE (1) PULL STATION PER FLOOR WILL BE REQUIRED WITH
 THE LOCATION NOTED ON THE PLAN SHEETS; 1ST FLOOR IN
 LOBBY UNDER HSTRB 0.1.10, 2ND FLOOR LOBBY AT LOCATION
 INDICATED ON PLAN UNDER HSTRB 1.1.7, 3RD FLOOR LOBBY
 UNDER HSTRB 1.4.2
  
  
 2) THE STROBES LOCATED WITHIN THE WOMENS AND MENS
 BATHROOMS ON THE 1ST AND 2ND FLOORS MAY NOT PROVIDED
 SUFFCIENT NOTIFICATION WITHIN THE INDIVIDUAL STALLS AT
 THE PROPOSED LOCATIONS. A CEILING MOUNT MAY SERVE THE
 AREA WITH BETTER COVERAGE.
  
 FINDING OUT THAT THE STROBE IS NOT VISIBLE AT THE TIME
 OF INSPECTION IN THOSE AREAS WOULD BE UNFORTUNATE.
 HOWEVER, SHOULD YOUR REVIEW FIND IT MEETS THE
 NOTIFCATION REQUIREMENTS, THE INSPECTION WOULD VERIFY.
  
 PLEASE REVIEW AND ENSURE APPLICABLE CODE COMPLIANCE.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  