| 2020-05-26 14:19:00 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT 20050293 |
| | 5/26/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE AN ENLARGED DRAWING OF THE NEW SHOWER THAT |
| | SHOWS THE DIMENSIONS FROM THE REAR FINISHED WALL OUT TO |
| | THE CENTERLINE OF THE THRESHOLD. REVIEW SECTION P2708.1 |
| | FBC RES. PRINTED BELOW AND SHOW COMPLIANCE: |
| | |
| | SHOWER COMPARTMENTS SHALL HAVE NOT LESS THAN 900 SQUARE |
| | INCHES OF INTERIOR CROSS-SECTIONAL AREA. SHOWER |
| | COMPARTMENTS SHALL BE NOT LESS THAN 30 INCHES IN |
| | MINIMUM DIMENSION MEASURED FROM THE FINISHED INTERIOR |
| | DIMENSION OF THE SHOWER COMPARTMENT, EXCLUSIVE OF |
| | FIXTURE VALVES, SHOWER HEADS, SOAP DISHES, AND SAFETY |
| | GRAB BARS OR RAILS. THE MINIMUM REQUIRED AREA AND |
| | DIMENSION SHALL BE MEASURED FROM THE FINISHED INTERIOR |
| | DIMENSION AT A HEIGHT EQUAL TO THE TOP OF THE THRESHOLD |
| | AND AT A POINT TANGENT TO ITS CENTERLINE AND SHALL BE |
| | CONTINUED TO A HEIGHT OF NOT LESS THAN 70 INCHES (1778 |
| | MM) ABOVE THE SHOWER DRAIN OUTLET. HINGED SHOWER DOORS |
| | SHALL OPEN OUTWARD. |
| | |
| | 2) INDICATE ON THE DRAWING THE LOCATION OF THE SHOWER |
| | DRAIN. PLEASE NOTE IF THE NEW DRAIN IS LOCATED IN THE |
| | CENTER OF THE SHOWER, THE HORIZONTAL DISTANCE FROM THE |
| | CENTERLINE OF THE NEW SHOWER DRAIN OUTLET TO THE |
| | CENTERLINE OF THE INLET OF THE EXISTING TRAP SHALL NOT |
| | EXCEED 30"- SECTION P3201.6 FBC RES. PLEASE NOTE THAT |
| | THE SHOWER DRAIN OUTLET SHALL NOT BE LESS THAN 1-1/2" |
| | IN DIAMETER- SECTION P2708.2 FBC RES. |
| | |
| | 3) PROVIDE A DETAIL FOR INSTALLATION OF THE NEW SHOWER |
| | RECEPTOR INDICATING THE HEIGHT OF THE NEW CURB |
| | THRESHOLD AND THE SLOPE OF THE FINISHED FLOOR TO THE |
| | DRAIN. INDICATE THE TYPE OF SHOWER RECEPTOR LINER TO BE |
| | USED- SECTIONS P2709.1 AND P2709.2 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |