| Plan Review Notes For Permit 20050288 |
| Permit Number |
20050288 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-05-22 16:45:02 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT A DIMENSIONED GENERATOR PAD PLAN. SPECIFY THE | | | SLAB REINFORCING AND THE GENERATOR TO SLAB ANCHORING. | | | INCLUDE THE TYPE OF FASTENERS, THE SIZE, THE EMBED | | | DEPTH, THE NUMBER AND THEIR LOCATION. PROVIDE THE WIND | | | DESIGN DATA ON THE DRAWING. FBC 107.2.1 | | | | | | 2) THE PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD | | | AREA. THE GENERATOR WILL HAVE TO BE ELEVATED ABOVE THE | | | BFE + A 2 FOOT FREEBOARD. CITY OF WEST PALM FLOOD | | | ORDINANCE. |
|