| 2020-06-10 16:43:23 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20050267 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE SPECS FOR THE TYPE OF PIPING USED. |
| | FBC FS 107.2.1 |
| | |
| | 2) PLEASE PROVIDE MODEL NUMBER AND SPECS FOR REGULATOR |
| | USED. FBC FS 107.2.1 |
| | |
| | 3) PLEASE PROVIDE GAS TABLE USED FOR SIZING THE 10 PSI |
| | PE GAS LINE. FBC FS 107.2.1 |
| | |
| | 4) PLEASE PROVIDE THE SPEC SHEETS FOR THE FLEXIBLE GAS |
| | LINE HOSE USED TO CONNECT THE GENERATOR. FBC FS 107.2.1 |
| | |
| | 5) PLEASE SHOW THAT THE GENERATOR IS COMPLYING WITH |
| | THE MANUFACTURER CLEARANCES FROM OPENABLE OPENINGS TO |
| | THE STRUCTURE. FBC FS 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |