| Notes |
| Date |
Text |
| 2020-08-03 13:22:28 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PREFAB GENERATOR PAD ENGINEERING THAT WAS | | | SUBMITTED HAS A REQUIRED MINIMUM WEIGHT OF 466 LBS. FOR | | | THE 22KW GENERATOR. THE 22 KW GENERATOR IN THE | | | SPECIFICATIONS THAT WERE SUBMITTED HAS A WEIGHT OF 445 | | | LBS. THE 445 LBS. GENERATOR DOES NOT MEET THE WEIGHT | | | REQUIRED BY THE PAD ENGINEERING. FBC 107 | | | | | | 2) SEE SIGNATURE REVIEW NOTES. |
|