| 2020-06-10 16:04:00 | REVIEW FBC-2017 MECHANICAL |
| | PERMIT -20050249 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE THE BTU?S OF THE GENERATOR AND ADD |
| | THEM TO THE TOTAL APPLIANCE BTU SHEET. THE BTU?S OF THE |
| | GENERATOR MUST BE INCLUDED IN THE SIZING OF THIS |
| | SYSTEM.THE ENTIRE SYSTEM MUST BE SIZED ACCORDING TO THE |
| | LONGEST LENGTH TO THE AN APPLIANCE. FBC FS 107.2.1 |
| | |
| | 2) PLEASE PROVIDE 1 LEGIBLE GAS LINE DIAGRAM SHOWING |
| | THE COMPLETE GASLINE ON THE 1 SHEET. PLEASE SHOW PIPE |
| | SIZES AND LENGTH ON EACH SECTION OF PIPE. PLEASE ALSO |
| | SHOW THE GAS METER AND HOW THE INTERIOR AND EXTERIOR |
| | GAS LINES ARE CONNECTED. FBC FS 107.2.1 |
| | |
| | 3) PLEASE SHOW THE APPLIANCE REGULATOR LOCATION ALONG |
| | WITH THE DRIP LEG AND SHUTOFFS AT EACH APPLIANCE. FBC |
| | FS 107.2.1 |
| | |
| | 4) PLEASE SHOW ACCESS PROVIDED FOR EACH MP REGULATOR AT |
| | THE APPLIANCES. FBC FG 410.1 AND FBC FG 410.2 |
| | 5) |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |
| 2020-06-09 14:55:14 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT- 20050249 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE SPECIFICATIONS FOR THE GENERATOR ( |
| | INCLUDE THE MODEL #). FBC FS 107.2.1 |
| | |
| | 2) PLEASE PROVIDE THE MODEL #?S FOR THE POOL HEATER, |
| | THE GAS FIREPLACE, AND THE WATER HEATER. FBC FS 107.2.1 |
| | |
| | 3) PLEASE SHOW THE MATERIAL USED FOR THIS UNDERGROUND |
| | GAS SYSTEM INSIDE THE STRUCTURE MEETS- FBC FG 404.17 |
| | |
| | 4) IS THIS SYSTEM RUNNING UNDERGROUND INSIDE THE |
| | STRUCTURE? IF SO, PLEASE SHOW HOW THIS SYSTEM MEETS- |
| | FBC FG 404.6 AND FBC FG 404.8 |
| | |
| | 5) PLEASE PROVIDE A LEGIBLE GAS LINE DIAGRAM SHOWING |
| | EACH MP REGULATOR AT THE APPLIANCES AND TYPE OF |
| | MATERIAL USED IN THE ENTIRE SYSTEM . FBC FS 107.2.1 |
| | |
| | 6) PLEASE PROVIDE THE PRESSURE DROP FOR THIS SYSTEM. |
| | FBC FS 107.2.1 |
| | |
| | 7) PLEASE SHOW ACCESS PROVIDED FOR EACH MP REGULATOR AT |
| | THE APPLIANCES. FBC FG 410.1 AND FBC FG 410.2 |
| | |
| | |
| | 8) THE MANUAL FOR THE GAS RANGE INDICATES A TOTAL OF |
| | 6-BURNERS AND 1 GRIDDLE. WITH A COMBINED TOTAL OF |
| | 110,000 BTU?S. THE DRAWING PRESENTED IN THIS PACKAGE IS |
| | INDICATING ONLY 77,200 BTU?S FOR THIS RANGE. PLEASE |
| | CORRECT THE BTU?S. FBC FS 107.2.1 |
| | |
| | 9) PLEASE PROVIDE THE TABLE NUMBERS USED TO SIZE THIS |
| | GAS PIPING SYSTEM. FBC FS 1.07.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |