2020-05-13 11:22:03ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) BOTH THE FLORIDA STATE AND THE MIAMI DADE PRODUCT
 APPROVALS HAVE EXPIRED - PLEASE PROVIDE UPDATED COPIES.
 FLORIDA STATE PRODUCT APPROVAL EXPIRES WHEN A NEW
 VERSION IS APPROVED THE NEW VERSION IS ( FL2533-R23)
 2) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT
 APPROVAL REQUIRES ADDITIONAL SIGNED AND SEALED
 ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR
 ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER PRESSURE
 THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL (-60) -
 SEE GENERAL LIMITATION NUMBER 7 (NOTE 5.7 ON FL STATE)
 ON THE PRODUCT APPROVAL. SIGNED AND SEALED DRAWINGS OR
 DOCUMENTS WILL NEED TO BE DIGITALLY SIGNED AND SEALED
 TO BE USED IN ELECTRONIC PLAN REVIEW.
  