Plan Review Notes
Plan Review Notes For Permit 20050175
Permit Number 20050175
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-06-03 14:18:57THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO SCOPE OF WORK
  
 THE TITLE BLOCK INDICATES DOOR REPAIR, THE APPLICATION
 INDICATES REPLACEMENT,
  
 PLEASE PROVIDE SPECIFIC DETAILS
  
  
 2) THERE IS NO INDICATION ON THE PLAN SHEET WHERE THE
 WORK IS TAKING PLACE.
  
 PLEASE PROVIDE A CLEAR INDICATION ON THE PLAN SHEET
 WHERE THE WORK IS LOCATED.
  
  
 3) THERE IS NO DOOR SCHEDULE INCLUDING FIRE RATINGS,
 CLOSERS, AND APPLICABLE CODE COMPLIANT HARDWARE.
  
 PLEASE PROVIDE.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  