| Plan Review Notes For Permit 20050144 |
| Permit Number |
20050144 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-07-21 09:13:53 | PREVIOUS COMMENTS NOT ADDRESSED. | | | | | | PREVIOUS COMMENTS REPOSTED: | | | | | | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE ARE NO INDICATIONS OF EXISTING FIRE SPRINKLER | | | OR FIRE ALARM SYSTEMS. | | | | | | ANY WORK ON THE WALLS AND CEILINGS AFFECT FIRE ALARM | | | DEVICES AND COVERAGE. | | | | | | ANY WORK ON THE FA SYSTEM SHALL BE DONE UNDER SPERATE | | | PERMITS AND SHOP DRAWINGS. | | | | | | PLEASE PROVIDE DETAILS AND PROVIDE AN APPLICABLE NOTE | | | OF ACKNOWLEDGEMENT. | | | | | | | | | | | | 2) THERE APPEARS TO BE NEW DOORS; HOWEVER, THERE IS NO | | | DOOR SCHEDULE. | | | | | | PLEASE PROVIDE DETAILS. | | | | | | | | | 3) THERE IS INDICATIONS OF NEW TILE; HOWEVER, THERE IS | | | NO UNDERLAYMENT. | | | | | | PER NFPA 31, EXISTING APARTMENT BUILDINGS | | | | | | 31.3.3 INTERIOR FINISH. | | | 31.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN | | | ACCORDANCE WITH SECTION | | | 10.2. | | | | | | PLEASE PROVIDE DETAILS. | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|