2020-07-21 07:50:30ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLAN IS NOT CLEAR AS TO WHERE NEW LED LIGHTS ARE GOING?
  
 FAN IN BREAKFAST ROOM IS IT NEW?
  
 NEED TO SHOW ELECTRIC IN NEW ISLAND AND LOCATION OF
 OUTLETS.
  
 NEED TO SHOW NEW LIGHTING AND OUTLETS EXACT LOCATIONS.
  
 REPLACING ALL OUTLETS AND SWITCHES REQUIRES ARC FAULT
 PROTECTION PER 406.4(D)(4)
  
 406.4(D) REPLACEMENTS. REPLACEMENT OF RECEPTACLES SHALL
 COMPLY WITH 40 6.4(D)(1) THROUGH (D)(6), AS APPLICABLE.
 ARC-FAULT CIRCUITINTERRUPTER TYPE AND GROUND-FAULT
 CIRCUIT-INTERRUPTER TYPE RECEPTACLES SHALL BE INSTALLED
 IN A READILY ACCESSIBLE LOCATION.
 (4) ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. WHERE A
 RECEPTACLE OUTLET IS SUPPLIED BY A BRANCH CIRCUIT THAT
 REQUIRES ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION AS
 SPECIFIED ELSEWHERE IN THIS CODE, A REPLACEMENT
 RECEPTACLE AT THIS OUTLET SHALL BE ONE OF THE
 FOLLOWING: (1) A LISTED OUTLET BRANCH-CIRCUIT TYPE
 ARC-FAULT CIRCUIT-INTERRUPTER RECEPTACLE (2) A
 RECEPTACLE PROTECTED BY A LISTED OUTLET BRANCH-CIRCUIT
 TYPE ARC-FAULT CIRCUIT-INTERRUPTER TYPE RECEPTACLE (3)
 A RECEPTACLE PROTECTED BY A LISTED COMBINATION TYPE
 ARCFAULT CIRCUIT-INTERRUPTER TYPE CIRCUIT BREAKER THIS
 REQUIREMENT BECOMES EFFECTIVE JANUARY 1, 2014.
  