| 2020-07-21 07:50:30 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | PLAN IS NOT CLEAR AS TO WHERE NEW LED LIGHTS ARE GOING? |
| | |
| | FAN IN BREAKFAST ROOM IS IT NEW? |
| | |
| | NEED TO SHOW ELECTRIC IN NEW ISLAND AND LOCATION OF |
| | OUTLETS. |
| | |
| | NEED TO SHOW NEW LIGHTING AND OUTLETS EXACT LOCATIONS. |
| | |
| | REPLACING ALL OUTLETS AND SWITCHES REQUIRES ARC FAULT |
| | PROTECTION PER 406.4(D)(4) |
| | |
| | 406.4(D) REPLACEMENTS. REPLACEMENT OF RECEPTACLES SHALL |
| | COMPLY WITH 40 6.4(D)(1) THROUGH (D)(6), AS APPLICABLE. |
| | ARC-FAULT CIRCUITINTERRUPTER TYPE AND GROUND-FAULT |
| | CIRCUIT-INTERRUPTER TYPE RECEPTACLES SHALL BE INSTALLED |
| | IN A READILY ACCESSIBLE LOCATION. |
| | (4) ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. WHERE A |
| | RECEPTACLE OUTLET IS SUPPLIED BY A BRANCH CIRCUIT THAT |
| | REQUIRES ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION AS |
| | SPECIFIED ELSEWHERE IN THIS CODE, A REPLACEMENT |
| | RECEPTACLE AT THIS OUTLET SHALL BE ONE OF THE |
| | FOLLOWING: (1) A LISTED OUTLET BRANCH-CIRCUIT TYPE |
| | ARC-FAULT CIRCUIT-INTERRUPTER RECEPTACLE (2) A |
| | RECEPTACLE PROTECTED BY A LISTED OUTLET BRANCH-CIRCUIT |
| | TYPE ARC-FAULT CIRCUIT-INTERRUPTER TYPE RECEPTACLE (3) |
| | A RECEPTACLE PROTECTED BY A LISTED COMBINATION TYPE |
| | ARCFAULT CIRCUIT-INTERRUPTER TYPE CIRCUIT BREAKER THIS |
| | REQUIREMENT BECOMES EFFECTIVE JANUARY 1, 2014. |
| | |