Plan Review Notes
Plan Review Notes For Permit 20050144
Permit Number 20050144
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-06-03 14:41:21THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS OF EXISTING FIRE SPRINKLER
 OR FIRE ALARM SYSTEMS.
  
 ANY WORK ON THE WALLS AND CEILINGS AFFECT FIRE ALARM
 DEVICES AND COVERAGE.
  
 ANY WORK ON THE FA SYSTEM SHALL BE DONE UNDER SPERATE
 PERMITS AND SHOP DRAWINGS.
  
 PLEASE PROVIDE DETAILS AND PROVIDE AN APPLICABLE NOTE
 OF ACKNOWLEDGEMENT.
  
  
  
 2) THERE APPEARS TO BE NEW DOORS; HOWEVER, THERE IS NO
 DOOR SCHEDULE.
  
 PLEASE PROVIDE DETAILS.
  
  
 3) THERE IS INDICATIONS OF NEW TILE; HOWEVER, THERE IS
 NO UNDERLAYMENT.
  
 PER NFPA 31, EXISTING APARTMENT BUILDINGS
  
 31.3.3 INTERIOR FINISH.
 31.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH SECTION
 10.2.
  
 PLEASE PROVIDE DETAILS.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  